Physical data (cont)
SI
UNIT 16JB 010 012 014 018 021
NOMINAL COOLING CAPACITY (kW) 108 122 137 186 211
RIGGING WEIGHT* (kg)
Absorber/Evaporator 2857 2890 2890 3652 3905
Generator/Condenser 1225 1238 1238 1565 1674
Total 4082 4128 4128 5217 5579
OPERATING WEIGHT (kg) 5100 5172 5208 6742 7146
LITHIUM BROMIDE SOLUTION CHARGE (L) 417 417 417 606 606
REFRIGERANT (WATER) CHARGE (L) 152 152 152 190 190
CHILLED WATER
Pipe Connection Size (in.) 44466
No. of Passes 22222
COOLING WATER
Pipe Connection Size (in.) 66666
No. of Passes
Absorber 22222
Condenser 11111
STEAM/HOT WATER
Pipe Connection Size (in.)
Steam Inlet/Hot Water Inlet 3 /2.5 3/2.5 3/2.5 4/3 4/3
Drain Outlet/Hot Water Outlet 1.25/2.5 1.25/2.5 1.25/2.5 1.25/3 1.25/3
UNIT 16JB 024 028 032 036 041
NOMINAL COOLING CAPACITY (kW) 245 279 326 362 413
RIGGING WEIGHT* (kg)
Absorber/Evaporator 4636 4704 5 875 6 001 8 167
Generator/Condenser 1987 2014 2 518 2 572 2 518
Total 6623 6718 8 393 8 573 10 685
OPERATING WEIGHT (kg) 8557 8807 10 958 11 202 13 761
LITHIUM BROMIDE SOLUTION CHARGE (L) 758 758 985 985 1213
REFRIGERANT (WATER) CHARGE (L) 246 246 265 265 341
CHILLED WATER
Pipe Connection Size (in.) 66888
No. of Passes 22222
COOLING WATER
Pipe Connection Size (in.) 888810
No. of Passes
Absorber 22222
Condenser 11111
STEAM/HOT WATER
Pipe Connection Size (in.)
Steam Inlet/Hot Water Inlet 6/4 6/4 6/4 6/4 6/6
Drain Outlet/Hot Water Outlet 1.5/4 1.5/4 2/4 2/4 2/6
UNIT 16JB 047 054 057 061 068
NOMINAL COOLING CAPACITY (kW) 479 539 574 618 680
RIGGING WEIGHT* (kg)
Absorber/Evaporator 8 393 9 755 9 982 12 024 12 705
Generator/Condenser 2 518 3 176 3 176 3 176 3 357
Total 10 911 12 931 13 158 15 200 16 062
OPERATING WEIGHT (kg) 14 115 17 100 17 480 19 910 20 860
LITHIUM BROMIDE SOLUTION CHARGE (L) 1213 1365 1365 1477 1477
REFRIGERANT (WATER) CHARGE (L) 341 663 663 1004 1004
CHILLED WATER
Pipe Connection Size (in.) 88888
No. of Passes 22222
COOLING WATER
Pipe Connection Size (in.) 10 10 10 10 10
No. of Passes
Absorber 22222
Condenser 11111
STEAM/HOT WATER
Pipe Connection Size (in.)
Steam Inlet/Hot Water Inlet 6/6 8/6 8/6 8/6 8/6
Drain Outlet /Hot Water Outlet 2/6 3/6 3/6 3/6 3/6
*Standard shipping configuration is 1-piece for sizes 010-047; 2-piece for sizes 054-068.