Example 4 — Setpoint Display Screen
To access this display from the LID default screen:
1. Press MENU.
2. Press SETPOINT.
Table 2, Example 4 — Setpoint Display Screen
Description
Configurable
Range
Units
Reference Point
Name
Default Value
Base Demand Limit
LCW Setpoint
ECW Setpoint
ICE BUILD Setpoint
40-100
20-120 (6.7-48.9)
20-120 (6.7-48.9)
20-60 (–6.7-15.6)
%
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DLM
lcw
sp
ecw
sp
ice
sp
100
50.0 (10.0)
60.0 (15.6)
40.0 ( 4.4)