Step 8 -- Optional EconoMi$er IV -- The optional
EconoMiSer IV comes flom file factory fully wired. Outdoor
air hoods must be installed. No field wiring is required for
standard outdoor dry bulb changeover operation. Field wiring
of accessory sensors is required for different operational
modes.
INSTALL OUTDOOR AIR HOODS -- Perform file follow-
ing procedure to install the outdoor-air hoods:
1. Economizer and barometric relief hoods abe located in the
condenser section under the slanted coil for shipping. See
Fig. 10. Barometric relief/power exhaust hood is shipped
inside of economizer hood. Remove screws that secure
the wooden rails of the hood assemblies to the unit. Save
screws. Slide complete assembly flom condenser section.
2. Remove the screws that secure file economizer and
b;uometfic relief/power exhaust hoods to the wooden
r;filing. Discard or recycle wooden rails. Save screws.
3. The barometric relief dmnper is secured to the economizer
panel for shipping. Remove the screw holding the baro-
metric relief &tmper to the panel. Dmnper should be free
to swing open during operation. See Fig. 11.
4. Hang the barometric relief/power exhaust hood on the
mounting flange on the economizer panel. Secure hood to
panel with screws saved from Step 2. See Fig. 11 and 12.
5. Align hole in flange of economizer panel with left edge of
hood. Hang economizer hood on the top flange of the
economizer panel by rotating hood until top flange of the
economizer hood engages the bent flange on the econo-
mizer panel. Rotate hood until hood is flush with the
economizer panel. Hood will support itself fl_)m flange.
Align holes in hood with holes in panel and secure
hood to panel with screws saved from Step 2. See
Fig. 11 and 13.
ECONOMI$ER IV STANDARD SENSORS
Outdoor-Air Temperature (OAT)Sensor- The outdoo>air
temperature sensor is a 10 to 20 mA device used to measure the
outdoo>air temperature. The outdoo>air temperature is used to
determine when the EconoMi$er IV can be used for flee cool-
ing. The sensor is factou-installed on the EconoMi$er IV in
the outdoor airstmam. The operating range of temperature
measurement is 40 to 100 E
MOUNTING /
FLANGE
ECONOMIZER
HOOD
POWER EXHAUST/
BAROMETRIC
RELIEF HOOD
\
ECONOMIZER BAROMETRIC
PANEL RELIEF DAMPER SCREW
Fig. 11 -- Hood Installation
POWER EXHAUST/
BAROMETRIC
RELIEF HOOD
POWER EXHAUST/
BAROMETRIC
f RELIEF HOOD
Fig. 12- Barometric Relief/Power Exhaust
Hood Flange
WOODEN RAILS
_ ECONOMIZER
HOOD
Fig. 10 -- Economizer and Barometric
Relief/Power Exhaust Hoods Shipping Positions
MOUNTING
FLANGE
ECONOMIZER
HOOD
Fig. 13- Economizer Flange
22