14
AIR THROW DATA
UNIT
CAPACITY
APPROXIMATE AIR THROW ft. (m)
Low Medium High
009 115v 11 (3.5) 15 (4.5) 21 ( 6.5)
012 115v 14 (4.2) 17 (5.1) 23 ( 7.0)
012 208/230v 14 (4.2) 17 ( 5.1) 23 (7.0)
018 208/230v 16 (5.0) 20 ( 6.2) 28 (8.5)
022 208/230v 19 (5.7) 23 ( 7.0) 31 (9.5)
SOUND RATINGS
Outdoor Units
Model Number Sound Power dBa Sound Pressure dBa
3 8 M FC(Q) 0 0 9 --- --- --- 1 67 57
3 8 M FC(Q) 0 1 2 --- --- --- 1 67 58
3 8 M FC(Q) 0 1 2 --- --- --- 3 67 58
38MFC017 / 38MFC018 --- --- ---3 70 60
3 8 M FC(Q) 0 2 2 --- --- --- 3 72 61
Indoor Units
Model Number
High Medium Low
Sound Power
dBa
Sound Pressure
dBa
Sound Power
dBa
Sound Pressure
dBa
Sound Power
dBa
Sound Pressure
dBa
4 0 M FC00 9 --- --- --- 1 52 43 48 39 43 34
4 0 M FC01 2 --- --- --- 1 53 44 49 40 45 36
4 0 M FC01 2 --- --- --- 3 53 44 49 40 45 36
4 0 M FC01 8 --- --- --- 3 55 45 51 41 47 37
4 0 M FC02 2 --- --- --- 3 60 50 56 46 52 42
4 0 M FQ0 0 9 --- --- --- 1 52/49 (Clg/Htg) 43/40 ( Clg/Htg) 48/44 (Clg/Htg) 39/35 (Clg/Htg) 43/39 (Clg/Htg) 34/ 30 (Clg/Htg)
4 0 M FQ0 1 2 --- --- --- 1 53/52 (Clg/Htg) 44/43 ( Clg/Htg) 49/47 (Clg/Htg) 40/38 (Clg/Htg) 45/52 (Clg/Htg) 36/ 33 (Clg/Htg)
4 0 M FQ0 1 2 --- --- --- 3 53/51 (Clg/Htg) 44/42 ( Clg/Htg) 49/45 (Clg/Htg) 40/36 (Clg/Htg) 45/40 (Clg/Htg) 36/ 31 (Clg/Htg)
4 0 M FQ0 1 7 --- --- --- 3 55/52 (Clg/Htg) 45/42 ( Clg/Htg) 51/48 (Clg/Htg) 41/38 (Clg/Htg) 47/43 (Clg/Htg) 37/ 33 (Clg/Htg)
4 0 M FQ0 2 2 --- --- --- 3 60/56 (Clg/Htg) 50/46 ( Clg/Htg) 56/52 (Clg/Htg) 46/42 (Clg/Htg) 52/48 (Clg/Htg) 42/ 38 (Clg/Htg)
NOTES:
1. Sound power r atings ar e per AHRI 270 and AHRI 350
2. Sound pressure ratings are estimated sound pressure, 3 feet (.91 m) from the unit, based on sound power data.
ELECTRICAL DATA
UNIT SIZE
OPER.
VOLTAGE
MAX / MIN*
COMPRESSOR OUTDOOR FAN INDOOR FAN
MCA
MAX FUSE
CB AMP
V --- P H --- H Z RLA LRA V --- P H --- H Z FLA HP W V --- P H --- H Z FLA HP W
9K
127 / 104 115--- 1 --- 6 0 5.3 10 1 1 5 --- 1 --- 60 0.7 0.31 23 11 5 --- 1 --- 60 0.3 0.020 15 19 30
12K
12K
253 / 187 2 08 --- 23 0 --- 1 --- 60
5.3 10
2 0 8 --- 23 0 --- 1 --- 60
0.3 0.33 24
2 0 8 --- 23 0 --- 1 --- 60
0.2 0.027 20 10 15
017K (HP)
018K (AC)
3.95 14 0.6 0.68 50 0.3 0.038 28 14 20
22K 9.7 17 0.6 0.72 53 0.4 0.061 45 16 25
*Permissible limits of the voltage range at which the unit will operate satisfactorily
LEGEND
FLA --- F u l l L o a d A m p s
LRA --- L o c k e d R o t o r A m p s
MCA --- Minimum Circuit Amps
RLA --- R a t e d Lo a d A m p s