CL-8
23XL PIC II SETUP2 TABLE CONFIGURATION SHEET
DESCRIPTION STATUS UNITS DEFAULT VALUE
Capacity Control
Proportional Inc Band
2 to 10 6.5
Proportional Dec Band
2 to 10 6.0
Proportional ECW Gain
1 to 3 2.0
VFD/Slide Valve Control
VFD Option
0/1 DSABLE/ENABLE DSABLE
VFD Gain
0.1 to 1.5 0.75
VFD Increase Step
1 to 5 % 2
VFD Minimum Speed
20 to 100 % 0
VFD Maximum Speed
50 to 100 % 100
Manual SV Temp Option
0/1 DSABLE/ENABLE DSABLE
Vedere la pagina 111