VFD FRAME SIZES
*Maximum limits only. Additional application limits apply that will reduce these ampacities.
AUXILIARY RATINGS*
*Factory wired to VFD.
†Minimum circuit ampacity of 15 amps.
FRAME SIZE MAX INPUT CURRENT* MAX OUTPUT CURRENT*
AA 440 442
BA 520 442
BB 520 520
CC 608 608
ITEM VOLTAGE
MAXIMUM
PROTECTIVE DEVICE
SIZE (AMPS)
WATTS
Controls, Oil Pump And Heater Circuit† 115 15
Oil Pump 115 1.48 130
Oil Sump Heater 115 4.35 500
Oil Vaporizer Heater Circuit† 115 15
Oil Vaporizer Heater 115 13 1500
Electrical data