Room Controller Configuration Setup — To con-
figure the room controller, press the Mode button for 5 sec-
onds. After 5 seconds, “10” will appear. This indicates that the
user is setting the first software configuration item. To display
the value of configuration item 10, press the Mode button
again. The value of the Heat/Cool vs Cooling only remote con-
figuration will be displayed along with the “Set Temp” icon to
indicate that the number displayed is the configuration data.
Refer to Table 7 for configuration values. To change the Heat/
Cool vs Cooling only remote Configuration, press the Up and
Down buttons. To move to the next setting, press the Mode
button again and the “10” will be displayed. Press the up button
and the display will change to “11.” Refer to Fig. 32.
The Mode button will toggle the display between the items and
the configuration value. The Up and Down buttons will change
either the index or the value, whichever is displayed at the time.
Press the Fan button to exit the Configuration Setup Mode.
This mode will exit automatically after 10 seconds of inactivi-
ty. Once a configuration value is changed, the last value
displayed will be the new configuration value for the room
controller.
NOTE: The only way to abort a configuration change is to
change the value back to its original value.
Table 7 — Room Controller Configuration Values
* Factory default.
1. Configuration Item 10: Heat Pump vs Cooling Mode
H — The Room Controller will allow and display the
following modes:
• Off
• Fan
• Auto
• Cool
•Dry
• Heat
C — The Room Controller will allow and display the fol-
lowing modes:
•Off
•Fan
• Cool
•Dry
2. Configuration Item 11: Room Thermistor Override
On — Room Thermistor Override is active. Units will be
controlled to the air temperature displayed via the Room
Controller.
Of (Off) — Room Thermistor Override is not active. All
units will be controlled to the room air thermistors located
on the units.
3. Configuration Item 12: Celsius vs Fahrenheit
C — Temperatures will be displayed in degrees Celsius.
F — Temperatures will be displayed in degrees Fahrenheit.
ITEM VALUE DESCRIPTION
10
H* Heat/Cool Remote
C Cooling Only Remote
11
On
Room Thermistor Override
Active.
Of*
Control and display room air
temperature at the room
controller. Room Thermistor
Override Inactive. Do not
display room air temperature
at the room controller and
control to unit room air
thermistor(s).
12
C*
Temperatures displayed in
degrees Celsius.
F
Temperatures displayed in
degrees Fahrenheit.
NOTE: When two louvers are closed, the fresh airflow towards the adjacent room is 50% higher than when
one louver is closed (with equal static external pressure).
Fig. 31 — Pressure Drop for Conditioned Air Supply to an Adjacent Room: One Louver Closed
Supply air duct to adjacent room
Airflow (cfm)
erusserp citats lanretxE (in.wg)
0
50
100
150 200
40KMC018,024
40KMQ01824
0.18
250
0.16
0.14
0.12
0.1
0.08
0.06
0.04
0.02
40KMC,KMQ 03036
0
Vedere la pagina 20
1 2 ... 16 17 18 19 20 21 22 23 24

Commenti su questo manuale

Nessun commento