TO CLEAN OR REPLACE DRAIN PAN
1. Place a plastic sheet on the floor to catch any water that
may spill from drain pan.
2. Remove the air intake and distribution assembly. Remove
the condensate water in the drain pan by pulling out the
rubber drain plug and letting water drain into a 3-gallon
bucket.
3. Remove screws holding the drain pan. Carefully hold the
drain pan to remove it from the assembly.
4. Re-install the drain pan using the appropriate number of
screws. Center and align the metal fan inlet orifice with
the fan. Ensure the fan spins freely.
TROUBLESHOOTING
See Table 9 and Fig. 35 for troubleshooting information.
Fault Code Once a failure occurs with the indoor unit in
operation, the green LED on the indoor unit flashes at intervals
of 0.5 seconds. The fault code is deduced from the number of
times the green LED flashes, blocking unit operation. Between
one flash cycle and the next one, a pause of 5 seconds elapses.
See Fig. 34.
USING THE EMERGENCY BUTTON — The Emergency
button is for use by a qualified service technician only. The
Emergency button is for use when the room controller is inop-
erative. Use a screwdriver to press the emergency button
through the metal protection grille. See Fig. 35.
Table 9 — Fault Codes
* When code is enabled.
Emergency Operation — When the unit is in the OFF mode
and the Emergency button is pressed for 5 seconds, the unit
will operate as follows:
Automatic mode
temperature preset to 72 F
automatic fan speed
louvers set automatically according to the operating mode
Timer function is cancelled
buzzer beeps
When the unit is ON and the Emergency button is pressed
for 5 seconds, the unit will operate as follows:
the unit is turned off
buzzer beeps
When a signal is received by the remote control, the unit
operates accordingly.
Do not use a screw driver to pry drain pan out of assembly.
It could damage the pan.
CODE DESCRIPTION
2 Condensate discharge pump
3 Room air sensor fault
4 Indoor unit coil sensor fault
6* Filter dirty
7 Outdoor unit failure
10 EEPROM corrupt
11 Card serial number damaged
12 Address or zone incomplete
13 Gas flow distributor corrupt
14 Outdoor air thermistor fault
G reen
LED
Red
LED
Yellow
LED
R emote control
signal receiver
E mergency
B utton
Fig. 35 — Warning Lamps and Emergency Button