19XRV PIC III SETUP1 TABLE CONFIGURATION SHEET
NOTE: No variables are available for CCN read operation. Forcing shall not be supported on service screens.
DESCRIPTION RANGE UNITS DEFAULT VA L U E
Comp Motor Temp Override
150 to 200
(66 to 93)
DEG F
(DEG C)
200
(93)
Cond Press Override
90 to 165
(621 to 1138)
PSI
(kPa)
125
(862)
Rectifier Temp Override
155 to 170
(68 to 77)
DEG F
(DEG C)
160
(71)
Inverter Temp Override
155 to 170
(68 to 77)
DEG F
(DEG C)
160
(71)
Comp Discharge Alert
125 to 200
(52 to 93)
DEG F
(DEG C)
200
(93)
Comp Thrust Brg Alert
165 to 185
(74 to 85)
DEG F
(DEG C)
175
(79)
Comp Thrust Brg Trip
160 to 185
(71 to 85)
DEG F
(DEG C)
185
(85)
Thrust Brg Reset Factor 1.0 to 3.0 1.4
Chilled Medium 0/1 WAT E R/ B RI N E WAT E R
Chilled Water Deadband
.5 to 2.0
(0.3 to 1.1)
ˆF
(ˆC)
1.0
(0.6)
Evap Refrig Trippoint
0.0 to 40.0
(–17.8 to 4.4)
DEG F
(DEG C)
33.0
(0.6)
Refrig Override Delta T
2.0 to 5.0
(1.1 to 2.8)
ˆF
(ˆC)
3.0
(1.7)
Evap Approach Alert
0.5 to 15
(0.3 to 8.3)
ˆF
(ˆC)
5.0
(2.8)
Cond Approach Alert
0.5 to 15
(0.3 to 8.3)
ˆF
(ˆC)
6.0
(3.3)
Condenser Freeze Point
–20 to 35
(–28.9 to 1.7)
DEG F
(DEG C)
34
(1.1)
Flow Delta P Display 0/1 DSABLE/ENABLE DSABLE
Evap Flow Delta P Cutout
0.5 to 50.0
(3.4 to 344.8)
PSI
(kPa)
5.0
(34.5)
Cond Flow Delta P Cutout
0.5 to 50.0
(3.4 to 344.8)
PSI
(kPa)
5.0
(34.5)
Cond Hi Flow Delta P Limit
0.5 to 50.0
(3.4 to 344.8)
PSI
(kPa)
50.0
(344.8)
Cond Hi Flow Alarm Option 0/1 DSABLE/ENABLE DSABLE
Water Flow Verify Time 0.5 to 5 MIN 5
Oil Press Verify Time 15 to 300 SEC 40
Recycle Control
Restart Delta T
2.0 to 10.0
(1.1 to 5.6)
DEG F
(DEG C)
5.0
(2.8)
Shutdown Delta T
0.5 to 4.0
(0.3 to 2.2)
DEG F
(DEG C)
1.0
(.0.6)
Spare Alert/Alarm Enable
Disable=0, Lo=1/3, Hi=2/4
Spare Temp #1 Enable 0 to 4 0
Spare Temp #1 Limit
–40 to 245
(–40 to 118)
DEG F
(DEG C)
245
(118)
Spare Temp #2 Enable 0 to 4 0
Spare Temp #2 Limit
–40 to 245
(–40 to 118)
DEG F
(DEG C)
245
(118)
312