
55
TERMINATION OF ICE BUILD — The ice build function
terminates under the following conditions:
1. Time Schedule — When the current time on the ice build
time schedule (OCCPC02S) is not set as an ice build time
period.
2. Entering Chilled Water Temperature — Ice build opera-
tion terminates, based on temperature, if the ICE BUILD
TERMINATION parameter is set to 0 (TEMP), the
ENTERING CHILLED WATER temperature is less
than the ICE BUILD SETPOINT, and the ICE BUILD
RECYCLE is set to DSABLE. If the ICE BUILD
RECYCLE OPTION is set to ENABLE, a recycle
shutdown occurs and recycle start-up depends on
the LEAVING CHILLED WATER temperature being
greater than the water/brine CONTROL POINT plus the
RESTART DELTA T temperature.
3. Remote Contacts/Ice Level Input — Ice build operation
terminates when the ICE BUILD TERMINATION param-
eter is set to 1 (CONTACTS) and the ICE BUILD
CONTACTS are open and the ICE BUILD RECYCLE is
set to DSABLE (0). In this case, the ICE BUILD
CONTACTS provide ice level termination control. The
contacts are used to stop the ice build function when a
time period on the ice build schedule (OCCPC02S) is set
for ice build operation. The remote contacts can still be
opened and closed to start and stop the chiller when a
specific time period on the ice build schedule is not set for
ice build.
4. Entering Chilled Water Temperature and ICE BUILD
Contacts — Ice Build operation terminates when the ICE
BUILD TERMINATION parameter is set to 2 (BOTH)
and the conditions described above in items 2 and 3 for
ENTERING CHILLED WATER temperature and ICE
BUILD CONTACTS have occurred.
NOTE: It is not possible to override the CHILLER START/
STOP, CONTROL POINT, and ACTIVE DEMAND LIMIT
variables from CCN devices (with a priority 4 or greater)
during the ice build period. However, a CCN device can
override these settings during 2-chiller lead/lag operation.
RETURN TO NON-ICE BUILD OPERATIONS — The ice
build function forces the chiller to start, even if all other sched-
ules indicate that the chiller should stop. When the ice build
function terminates, the chiller returns to normal temperature
control and start/stop schedule operation. The CHILLER START/
STOP and CONTROL POINT return to normal operation. If the
CHILLER START/STOP or CONTROL POINT has been forced
(with a device of less than 4 priority) before the ice build func-
tion started, when the ice build function ends, the previous forces
(of less than 4 priority) are not automatically restored.
Attach to Network Device Control — The Service
menu includes the ATTACH TO NETWORK DEVICE
screen. From this screen, the operator can:
• enter the time schedule number (if changed) for
OCCPC03S, as defined in the NET_OPT screen
• attach the ICVC to any CCN device, if the chiller has been
connected to a CCN network. This may include other PIC-
controlled chillers.
• upgrade software
Figure 25 shows the ATTACH TO NETWORK DEVICE
screen. The LOCAL parameter is always the ICVC module
address of the chiller on which it is mounted. Whenever the
controller identification of the ICVC changes, the change is
reflected automatically in the BUS and ADDRESS columns
for the local device. See Fig. 17. Default address for local
device is BUS 0 ADDRESS 1.
When the ATTACH TO NETWORK DEVICE screen is
accessed, information can not be read from the ICVC on any
device until one of the devices listed on that screen is attached.
The ICVC erases information about the module to which it was
attached to make room for information on another device.
Therefore, a CCN module must be attached when this screen is
entered.
To attach any CCN device, highlight it using the
softkey and press the softkey. The message
“UPLOADING TABLES, PLEASE WAIT” displays. The
ICVC then uploads the highlighted device or module. If
the module address cannot be found, the message “COMMU-
NICATION FAILURE” appears. The ICVC then reverts back
to the ATTACH TO DEVICE screen. Try another device or
check the address of the device that would not attach. The
upload process time for each CCN module is different. In
general, the uploading process takes 1 to 2 minutes. Before
leaving the ATTACH TO NETWORK DEVICE screen, select
the LOCAL device. Otherwise, the ICVC will be unable to
display information on the local chiller.
ATTACHING TO OTHER CCN MODULES — If the chill-
er ICVC has been connected by CCN wiring to the CCN net-
work or other PIC controlled chillers, the ICVC can be used to
view or change parameters on the other controllers. Other PIC
III chillers can be viewed and set points changed (if the other
unit is in CCN control), if desired, from this particular ICVC
module.
If the module number is not valid, the “COMMUNICA-
TION FAILURE” message will show and a new address
number must be entered or the wiring checked. If the module is
communicating properly, the “UPLOAD IN PROGRESS”
message will flash and the new module can now be viewed.
Whenever there is a question regarding which module on
the ICVC is currently being shown, check the device name
descriptor on the upper left hand corner of the ICVC screen.
See Fig. 25.
When the CCN device has been viewed, the ATTACH TO
NETWORK DEVICE table should be used to attach to the PIC
that is on the chiller. Move to the ATTACH TO NETWORK
DEVICE table (LOCAL should be highlighted) and press the
softkey to upload the LOCAL device. The ICVC
for the 19XRV will be uploaded and default screen will display.
NOTE: The ICVC will not automatically reattach to the local
module on the chiller. Press the softkey to attach to
the LOCAL device and view the chiller operation.
Fig. 25 — Example of Attach to Network
Device Screen
a19-1743
Commenti su questo manuale