
#:
On 9/20/04, Operations personnel at Hope Creek identified a refrigerant leak after noticing the
formation of ice on a skid mounted CUNO filter. Immediate actions performed included securing
the chiller, evacuating the area for personal safety issues due to the presence of R-114
refrigerant, and pumping down the chiller refrigerant charge to the storage vessel.
Because of the leak, the 1BK403 chiller was declared inoperable. Station personnel
subsequently determined that improper installation and assembly of the CUNO filter caused the
leak.
Initially, maintenance personnel considered that the refrigerant leak was coming from the filter
o-ring gasket; however a follow-up maintenance inspection found the filter housing to be slightly
tilted from vertical, and missing the band clamp used to ensure that the filter is securely
fastened in its cradle. A review of work history indicated that the filter cartridges had recently
been replaced in August 2004 during a planned maintenance activity.
To repair the leak, maintenance personnel removed the filter sump, re-welded the filter cradle
to the chiller skid, and installed a new filter head o-ring gasket and sump. Post-maintenance
pressure testing of the chiller verified that the leak was repaired, and 1,150 lbs of R-114
refrigerant was added to the chiller prior to releasing it to station operators for operability
testing. Satisfactory testing of the chiller was completed and the LCO exited at approximately
0447
hours on 9/25/04.
During the repair process, station personnel performed walk-downs on all Hope Creek
centrifugal chillers and confirmed that their installed piping and filter configuration were
satisfactory. A review of maintenance procedures was also performed at that time, and the filter
manufacturer was also consulted.
As a result of these reviews, it was determined: 1) That the leak occurred due to improper
installation of the CUNO filter, 2) That the existing maintenance procedure contained
insufficient guidance for proper removal/installation of the filter sump and for the replacement of
CUNO filter elements, and 3) That the missing band clamp probably did not contribute to the
formation of the leak, although it does provide additional support to the filter and copper
refrigerant line.
Commenti su questo manuale