These starters operate by reducing the starting voltage. The
starting torque of a motor at full voltage is typically 125%
to 175% of the running torque. When the voltage and the
current are reduced at start-up, the starting torque is reduced
as well. The objective is to reduce the starting voltage to just
the voltage necessary to develop the torque required to get
the motor moving. The voltage and current are then ramped
up in the desired period of time. The voltage is reduced through
the use of silicon controlled rectifiers (SCR). Once full volt-
age is reached, a bypass contactor is energized to bypass the
SCRs.
When voltage is supplied to the solid-state circuitry, the
heat sinks within the starter are at line voltage. Do not
touch heat sinks while voltage is present or serious in-
jury will result.
There are a number of LEDs (light-emitting diodes) that
are useful in troubleshooting and starter check-out on
the Benshaw, Inc. solid-state starters. These are used to
indicate:
voltage to the SCRs
SCR control voltage
power indication
proper phasing for rotation
start circuit energized
overtemperature
ground fault
current unbalance
run state
These LEDs (on Benshaw, Inc. solid-state starters) are fur-
ther explained in the Check Starter and Troubleshooting Guide
sections, pages 49 and 68.
Unit Mounted Wye-Delta Starter (Optional)
The 23XL machine may be equipped with a wye-delta starter
mounted on the unit. This starter is intended for use with
low-voltage motors (under 600 v). It reduces the starting cur-
rent inrush by connecting each phase of the motor windings
into a wye configuration. This occurs during the starting pe-
riod when the motor is accelerating up to speed. After a time
delay, once the motor is up to speed, the starter automati-
cally connects the phase windings into a delta configuration.
1—Pilot Relays (PR1 to PR5)
2—Circuit Breaker 4
3—Silicon Controlled Rectifier (SCR) (One of 6) (Hidden)
4—Circuit Breaker 3
5—Solid-State Controller
6—Circuit Breaker 2
7—Circuit Breaker 1
8—Ammeter (Optional)
9—Voltmeter (Optional)
10 Overload Calibration Unit
11 Field Wiring Terminal Strips (TB2 and TB3) (Hidden)
12 Starter Management Module (SMM)
13 Starter Access Door
Fig. 8A Cutler-HammerT Solid-State Starter,
Internal View
1—Field Wiring Terminal Strips (TB2 and TB3)
2—Circuit Breakers 1, 2, 3, 4
3—Overload Calibration Unit
4—Solid-State Controller
5—SCR LED (One of 6)
6—Starter Fault and Run LEDs
7—Voltmeter (Optional)
8—Ammeter (Optional)
9—Silicon Controlled Rectifier
(SCR) (One of 6)
10 Voltage LED
11 Starter Management Module (SMM)
12 Pilot Relays (PR1 to PR6)
13 Starter Access Door
Fig. 8B Benshaw, Inc. Solid-State Starter,
Internal View