
LOCAL INTERFACE DEVICE (LID) — The LID is mounted
in the control center and allows the operator to interface with
the PSIO or other CCN devices. It is the input center for all
local machine set points, schedules, set up functions, and op-
tions. The LID has a stop button, an alarm light, 4 buttons
for logic inputs, and a display. The function of the 4 buttons
or ‘‘softkeys’’ are menu driven and are shown on the display
directly above the keys.
6-PACK RELAY BOARD — This device is located in the
control center and a cluster of 6 pilot relays, energized by
the PSIO, for the oil heater (Frame 1 and 2 machines), spare
alarm, optional hot gas bypass relay, and motor cooling
solenoids.
8-INPUT MODULES (Optional) — One optional module is
factory installed in the control center when ordered. There
can be up to 2 of these modules per chiller with 8 spare in-
puts each. They are used whenever chilled water reset, de-
mand reset, common supply/return sensors, or reading a spare
sensor is required. The sensors or 4 to 20 mA signals are
field installed.
The spare temperature sensors must have the same
temperature/resistance curve as the other temperature sen-
sors on this unit. These sensors are 5,000 ohm at 75 F
(25 C).
OIL HEATER CONTACTOR RELAY (1C) (Frame 1 and 2
Only) — This contactor relay is located in the power panel
and operates the heater at either 115 or 230 v. It is controlled
by the PIC to maintain oil temperature during machine
shutdown.
HOT GAS BYPASS RELAY (3C) (Optional) — This relay
contactor located in the power panel, controls the opening of
the hot gas bypass solenoid valve. The PIC energizes the
relay during low load, low compression ratio conditions.
CONTROL TRANSFORMERS (T1-T4) — These trans-
formers convert incoming control voltage to either 21-vac
supply power for the PSIO module, LID, and options mod-
ule, or 24-vac power supply for the power panel, control re-
lays, 6-pack relay board, oil solenoid valve, oil level switch,
slide valve solenoids, and VI (optional) actuator solenoids.
CONTROLAND OIL HEATER VOLTAGE SELECTOR (S1)
— It is possible to utilize either 115 v or 230 v
incoming control power in the power panel. The switch is
set to the voltage used at the jobsite.
VARIABLE CONTACTOR RELAY (2C) (Optional) — This
contactor relay is located in the power panel. The PIC en-
ergizes the relay to move the slide valve stop to the high VI
position based on system compression ratio.
TEMPERATURE SENSORS — The temperature sensors sense
the temperature of oil, refrigerant, water, and the motor through-
out the machine.
PRESSURE TRANSDUCERS — The pressure transducers
sense the pressure of oil and refrigerant throughout the
machine.
LID Operation and Menus (Fig. 17 - 23)
GENERAL
• The LID display will automatically revert to the default
screen after 15 minutes if no softkey activity takes place
and if the machine is not in the PUMPDOWN mode
(Fig. 17).
• When not showing the default screen, the upper right-
hand corner of the LID always displays the name of the
screen that you have entered (Fig. 18).
• The LID may be configured in English or SI units through
the LID configuration screen.
• Local Operation — By pressing the LOCAL
softkey, the
PIC is now in the LOCAL operation mode, and the control
will accept modification to programming from the LID only.
The PIC will use the Local time schedule to determine ma-
chine start and stop times.
• CCN Operation — By pressing the CCN
softkey, the
PIC is now in the CCN operation mode. The control will
accept modifications from any CCN interface or module
with the proper authority, as well as the LID. The PIC will
use the CCN time schedule to determine start and stop times.
ALARMS AND ALERTS — Alarm (*) and alert (!) status
are indicated on the Status tables. An alarm (*) will shut down
the compressor. An alert (!) notifies the operator that an un-
usual condition has occurred. The machine will continue to
operate when an alert is shown.
Alarms are indicated when the control center alarm light
(!) flashes on the LID panel. The alarm message is viewed
on the default screen and an additional message and trouble-
shooting information are sent to the alarm history screen.
When an alarm is detected, the LID default screen will
freeze (stop updating) at the time of alarm. The freeze en-
ables the operator to view the machine conditions at the time
of alarm. The Status tables will show the updated informa-
tion. Once all alarms have been cleared (by pressing the
RESET
softkey), the default LID screen will return to nor-
mal operation.
Fig. 17 — LID Default Screen
Fig. 18 — LID Service Screen
17
Commenti su questo manuale