Table 5 — Capacity Overrides
OVERRIDE
CAPACITY
CONTROL
VIEW/MODIFY
ON LID
TABLE
FIRST STAGE SETPOINT
SECOND STAGE
SET POINT
OVERRIDE
TERMINATION
Default
Value
Configurable
Range
HIGH CONDENSER
PRESSURE
EQUIPMENT SERVICE1 230 psi (1586 kPa) 150 to 250 psi
(1034 to 1724 kPa)
>Override Set point
+5 psi (35 kPa)
,Override Set Point
HIGH MOTOR
TEMPERATURE
EQUIPMENT SERVICE1 .200 F
(93 C)
150 to 200 F
(66 to 93 C)
.Override Set point
+10F(6C)
,Override Set Point
LOW REFRIGERANT
TEMPERATURE
(REFRIGERANT
OVERRIDE AT
TEMPERATURE)
EQUIPMENT SERVICE1 ,2F(1C)
Above Trippoint
2to5F
(1 to 3 C)
,Trippoint +
(Override DT—
1 F [0.56 C])
.Trippiont +
(Override DT + 2 F [1.2 C])
MANUAL
SLIDE VALVE
TARGET
CONTROL
ALGORITHM
MAINT01
Automatic −20 to 20
Counts
Manual control
cannot default
active control
Release of
Manual Control
MOTOR LOAD —
ACTIVE
DEMAND LIMIT
STATUS01 100% 40 to 100% >105% of
Set Point
2% Lower
Than Set Point
NOTE: [ ] indicates HFC-134a values.
Condenser Freeze Prevention — This control al-
gorithm helps prevent condenser tube freeze up by energiz-
ing the condenser pump relay. If the pump is controlled by
the PIC, starting the pump will help prevent the water in the
condenser from freezing. Condenser freeze prevention can
occur whenever the machine is not running except when it
is actively in Pumpdown or in Pumpdown Lockout with the
freeze prevention disabled (refer to Control Test table,
Pumpdown/Terminate Lockout screens). See Fig. 21. When
Pumpdown Lockout is initiated, if the CONDENSER
REFRIG TEMP is less than 40 F (4.4 C), then condenser
freeze prevention shall be disabled until termination of pump-
down lockout.
When the CONDENSER REFRIG TEMP is less than or
equal to the CONDENSER FREEZE POINT or the EN-
TERING CONDENSER WATER temperature is less than or
equal to the CONDENSER FREEZE POINT, then the CON-
DENSER WATER PUMP shall be energized until the CON-
DENSER REFRIG TEMP is greater then the CONDENSER
FREEZE POINT plus 5° F (2.7° C). An alarm will be gen-
erated if the machine is in PUMPDOWN mode and the pump
is energized. An alert will be generated if the machine is not
in PUMPDOWN mode and the pump is energized.
Either of the above on requirements may independently
result in the CONDENSER WATER PUMP being ener-
gized. However, both sets of off requirements must be met
in order for the pump to be deenergized.
Tower-Fan Relay — The tower fan relay, located in the
starter, is controlled by the PIC to energize and deenergize
as the pressure differential between cooler and condenser ves-
sels changes in order to prevent low condenser water tem-
perature and to maximize machine efficiency. The
tower-fan relay can only accomplish this if the relay has been
added to the cooling tower temperature controller. TheTOWER
FAN RELAY is turned on whenever the CONDENSER WA-
TER PUMP is running, flow is verified, and the difference
between cooler and condenser pressure is more than 50 psi
(433 kPa) or ENTERING CONDENSER WATER is greater
than 85 F (29 C). The TOWER FAN RELAY is deenergized
when the condenser pump is off, flow is lost, the evaporator
refrigerant temperature is less than the override temperature,
or the differential pressure is less than 45 psi (310 kPa) and
ENTERING CONDENSER WATER is less than 80 F (27 C).
IMPORTANT: A field supplied water temperature con-
trol system should be installed. The system should main-
tain the leaving condenser water temperature at a tem-
perature that is 18 F (10 C) above the leaving chilled
water temperature.
The tower fan relay control is not a substitute for a job-
site condenser water temperature control. When used with
a Water Temperature Control system, the tower fan re-
lay control can be used to help prevent low condenser
water temperatures.
Auto. Restart After Power Failure — This option
may be enabled or disabled, and may be viewed/modified on
the Equipment Configuration menu Config table. If enabled,
the chiller will start up automatically after a single cycle drop-
out, low, high, or loss of voltage has occurred, and the power
is within ±10% of normal. The start inhibit timers are ig-
nored during this type of start-up.
31