
Once the _lly occupied &impel position has been deter-
mined, set the maximum dmnper demand control ventilation
potentiometer to this position. Do not set to the maximum
position as this can result in over-ventilation to the space and
potential high humidity levels.
CO.2 Sensor Configuration -- Tile CO2 sensor has preset
standard voltage settings that can be selected anytime after the
sensor is powered up. See Table 4.
Use setting 1 or 2 for CmTier equipment.
1. Press Clem and Mode buttons. Hold fit least 5 seconds
until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appeal:
3. Use the Up/Down button to select the preset numbel: See
Table 4.
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO2 sensor can be changed any-
time after the sensor is energized. Follow the steps below to
change the non-standard settings:
1. Press Clem and Mode buttons. Hold fit least 5 seconds
until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appem:
3. Use the Up/Down button to toggle to the NONSTD menu
and press Enter.
4. Use the Up/Down button to toggle through each of the
nine variables, starting with Altitude, until the desired set-
ting is reached.
5. Press Mode to move through the vmiables.
6. Press Enter to lock in the selection, then press Mode to
continue to the next variable.
Dehumidification of Fresh Air with DCV (Demand Con-
trolled Ventilation) Control --Information from ASHRAE
(American Society of Heating, Refrigeration, and Air Condi-
tioning Engineers) indicates that the lmgest humidity load on
any zone is the fresh air introduced. For some applications, a
device such as a 62AQ energy recoveU unit is added to reduce
the moisture content of the fresh air being brought into the
building when the enthalpy is high. In most cases, the normal
heating and cooling processes are more than adequate to re-
move the humidity loads for most commercial applications.
This makes the control of the of the dehumidification device
simple when using the enthalpy or differential enthalpy sensol:
The enthalpy sensor or differential enthfdpy sensor is installed
on the equipment to determine economizer operation. The high
enthalpy signal from the enthalpy sensor or differential en-
thalpy sensor can be used to turn on the outdoor air moisture
removal device any time fl'esh air is required for the space.
The energy recoveU device should be sized for maximum
latent and sensible conditioning fit maximum ventilation on a
design day. A cfdculation for leaving-air temperature on a low
ambient, low ventilation day should also be done to determine
the mixed-air temperature of the return and pre-conditioned
outside all: The design should produce an air temperature
somewhat ne_u room conditions to prevent reheat of the air
mixture. The energy recovery device should be interlocked
with the heat to turn off the device when in the heat mode.
Step 9 -- Install All Accessories -- After all of the
factory-installed options have been adjusted, install all field-
installed accessories. Refer to the accessory installation instruc-
tions included with each accessory. Consult the C_rier Price
Pages or RTU (rooftop unit) Building software for accessory
package numbers for pm-ticulm applications.
SETTING
1
2
3
4
5
6
7
8
9
Table 4-- 002 Sensor Standard Settings
EQUIPMENT ANALOG
OUTPUT
Interface w/Standard
Building Control System
Economizer
Health & Safety
Parking/Air Intakes/
Loading Docks
OUTPUT
Proportional
Proportional
Exponential
Proportional
Proportional
Exponential
Exponential
Proportional
Proportional
VENTILATION
RATE
(cfm/Pereon)
Any
Any
Any
15
20
15
2O
O-1OV
4-20 mA
2-10V
7-20 mA
O-1OV
4-20 mA
O-1OV
4-20 mA
0-10V
4-20 mA
O-1OV
4-20 mA
0-10V
4-20 mA
O-1OV
4-20 mA
0-10V
4-20 mA
CO2
CONTROLRANGE
(ppm)
0-2000
0-2000
0-2000
0-1100
O- 900
0-1100
0- 900
0-9999
0-2000
OPTIONAL
RELAY SETPOINT
(ppm)
1000
1000
1100
1100
900
1100
900
5000
7OO
RELAY
HYSTERESIS
(ppm)
5O
5O
5O
5O
5O
5O
5O
5O0
5O
28
Commenti su questo manuale