Carrier 50PG03-07 Specifiche Pagina 47

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 46
4. RemovefilejumperacrossTandTl.Theactuatorshould
drivefullyclosed.
5. ReturnEconoMi$erIV settingsandwMngto normal
aftercompletingtroubleshooting.
ECONOMISER[V TROUBLESHOOTINGCOMPLE-
TION-- ThisprocedureisusedtoreturntheEconoMi$erIV
tooperation.Notroubleshootingortestingisdonebyperform-
ingthefollowingprocedure.
1. DisconnectpoweratTRandTRI.
2. Setenthalpypotentiometertoprevioussetting.
3. SetDCVmaximumpositionpotentiometertoprevious
setting.
4. Setminimumposition,DCVsetpoint,andexhaust
potentiometerstoprevioussettings.
5. Remove620-ohmresistorfromterminalsSRand+.
6. Remove1.2kilo-ohmcheckoutresistorfromterminals
Soand+.Ifused,leconnectsensorfromtermin_dsSoand
+.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo-ohm resistor from T and TI. Reconnect
wiles at T and TI.
10. Remove jumper from P to PI. Reconnect device at P and
PI.
11. Apply power (24 vac) to termin_ds TR and TRI.
Phase Loss Protection -- The phase loss protection
option will monitor the three-phase electric;d system to provide
phase reversal and phase loss protection.
PHASE REVERSAL PROTECTION -- If the control sens-
es an incorrect phase rekitionship, the rekiy (KI) will be de-
energized (opening its contact). If the phase relationship is
correct, the relay will be energized. The control has a self-
bypass function after a pre-set time. If the control determines
that the three phases stay in a correct relationship for 10 con-
secutive minutes, the rekiy will stay energized regardless of the
phase sequence of three inputs as long as 24-vac control
voltage is applied. This self-bypass lhnction will be reset if _dl
three phases are restored in a phase loss event.
PHASE LOSS PROTECTION-- If the reverse rotation
board senses any one of the three phase inputs has no AC volt-
age, the relay will be deenergized (opening its contact). This
protection is always active as long as 24-vac control voltage is
applied, and is not affected by the self bypass function of the
phase sequence monitoring function. Howevel: in the event of
phase loss, the relay will be re-energized only if all three phases
me restored and the three phases me in the correct sequence.
A red LED is provided to indicate the function of the board.
See the table below.
LED STATUS FUNCTION
Relay contact open (phase loss or phase
On Continuously Relay contact closed (normal operation).
Blinking reversal has occurred) -- No power will be
supplied to the control system.
Off 24 vac control power not present (off).