Carrier GTR040-420 Specifiche Pagina 28

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 27
28
Low Entering Fluid Temperature Unloading
When the
entering fluid temperature is below the control point, the con-
trol will attempt to remove 25% of the current stages being
used. If exactly 25% cannot be removed, the control removes
an amount greater than 25% but no more than necessary. The
lowest stage will not be removed.
Low Cooler Suction Temperature
To avoid freezing the
cooler, the control will compare the circuit Cooler Suction tem-
perature (T5/T6) with a predetermined freeze point. If the cool-
er fluid selected is Water, the freeze point is 34 F (1.1 C). If the
cooler fluid selected is Med. Brine, the freeze point is COOL
set point CSP.3 minus 8° F (4.4° C).
If the cooler suction temperature is 24° to 29° F (13.3° to
16.1° C) below the cooler leaving water temperature and is also
2° F (1.1° C) less than the freeze point for 5 minutes, Mode 7
(Circuit A) or Mode 8 (Circuit B) is initiated and no additional
capacity increase is allowed. The circuit will be allowed to run
in this condition. If the cooler suction temperature is more than
30° F (16.7° C) below the cooler leaving water temperature
and is also 2° F (1.1° C) below the freeze point for 10 minutes,
the circuit will be stopped without going through pumpdown.
Brine Freeze Set Point
If the cooler medium is glycol or
other suitable corrosion-inhibited antifreeze solution, then
CSP.3 should be set to the freeze point of the solution. This will
allow proper unit operation and prevent unnecessary Low
Cooler Suction Temperature and Cooler Freeze Protection
Alarms.
Cooler Freeze Protection
The control will try to prevent
shutting the chiller down on a Cooler Freeze Protection alarm
by removing stages of capacity. The control uses the same
freeze point logic as described in the Low Cooler Suction Tem-
perature section above. If the cooler leaving fluid temperature
is less than the freeze point plus 2.0° F (1.1° C), the control will
immediately remove one stage of capacity. This can be repeat-
ed once every 30 seconds.
MOP (Maximum Operating Pressure) Override
The con-
trol monitors saturated condensing and suction temperature for
each circuit. Based on a maximum operating set point (saturat-
ed suction temperature), the control may lower the EXV posi-
tion when system pressures approach the set parameters.
High Condensing Temperature Unloading
Every 10 sec-
onds the control checks for the conditions described below.
Unloaders and compressors will be cycled as needed to reduce
the saturated condensing temperature to below the configured
maximum condensing temperature. The factory default maxi-
mum condensing temperature is 154 F. If the condensing tem-
perature of a circuit is below the maximum condensing temper-
ature and within 12° of the limit, then the circuit capacity is not
allowed to increase. If the condensing temperature of a circuit
is below maximum condensing temperature and within 2° of
the limit and rising for 60 seconds, then an unloader will turn
on or a compressor will shut off to reduce unit capacity. If the
saturated condensing temperature is above the maximum con-
densing temperature, then unloaders will immediately turn on
or compressors will turn off to reduce unit capacity.
Head Pressure Control
COMFORTLINK UNITS (With EXV) The Main Base
Board (MBB) controls the condenser fans to maintain the low-
est condensing temperature possible, and thus the highest unit
efficiency. The fans are controlled by the saturated condensing
temperature set point which is 113 F (45 C) as a factory default.
The fans can also be controlled by a combination of the saturat-
ed condensing temperature, EXV position and compressor su-
perheat. Fan control is a configurable decision and is deter-
mined by the Head Pressure Control Method (HPCM) setting
in the Configuration Mode under the OPT1 sub-mode.
The default control mode is setpoint control (HPCM = 2)
where the fans modulate based on highest saturated condensing
temperature (T3 or T4) of the two refrigerant circuits. When
either T3 or T4 exceeds the head pressure set point, the MBB
will turn on an additional stage of fans. For the first 10 minutes
of each circuit operation, the head pressure set point is raised
by 10° F (5.6° C). If Motormaster® control is present, the set
point is raised 15° F (8.3° C) or an additional 5° F (2.8° C) if
within the first 10 minutes of operation in each circuit. The
Motormaster control offsets apply to the first additional stage
of fans only. The MBB will turn off a fan stage when T3 and
T4 are both below the head pressure set point by 35° F
(19.4° C). At each change of a fan stage, the control will wait
for 35 seconds for head pressure to stabilize unless T3 and T4
is greater than 125 F (51.6 C), in which case all MBB-
controlled fans start immediately. If T3 and T4 are greater than
95 F (35.0 C) just prior to circuit start-up, all MBB-controlled
fan stages are turned on to prevent excessive discharge pres-
sure during pulldown. Fan sequences are shown in Fig. 18.
For EXV control (HPCM = 1), when the position of the
EXV is fully open, T3 and T4 are less than 78 F (25.6 C), and
superheat is greater than 40° F (22.2° C), fan stages will be re-
moved. When the valve is less than 40% open, or T3 and T4
are greater than 113 F (45 C), fan stages will be added. For the
first 10 minutes of each circuit operation, the head pressure set
point is raised by 10° F (5.6° C). If Motormaster control is
present, the set point is raised 15° F (8.3° C) or an additional
5° F (2.8° C) if within the first 10 minutes of operation in each
circuit. The Motormaster control offsets apply to the first addi-
tional stage of fans only. At each change of the fan stage, the
system will wait 35 seconds to allow the head pressure to stabi-
lize unless either T3 or T4 is greater than 125 F (51.6 C), in
which case all MBB-controlled fans will start immediately.
This method allows the unit to run at very low condensing tem-
peratures at part load.
Motormaster Option
For low-ambient operation below
0° F (18.0 C), the lead fan(s) in each circuit can be equipped
with the Motormaster controls as a factory or field-installed
47
46
45
44
43
42
41
0 200 400 600 800 1000
TIME (SECONDS)
2 STARTS
3 STARTS
DEADBAND EXAMPLE
L
WT (F)
MODIFIED
DEADBAND
STANDARD
DEADBAND
8
7
6
5
L
WT (C)
Fig. 17 Deadband Multiplier
LEGEND
LWT
Leaving Water Temperature
Vedere la pagina 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 103 104

Commenti su questo manuale

Nessun commento