Table 19B Example of Configuring Dual Chiller Control (Slave Chiller)
NOTES:
1. Slave CCN Address must be different than Master.
2. Slave CCN Bus Number must be the same as Master.
3. Slave does not require LLBL, LLBD or LLDY to be configured.
SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENT
OPT2 CTRL CONTROL METHOD
CTRL 0 SWITCH SCROLLING STOPS
0VALUE FLASHES
3SELECT 3
CTRL 3 CCN CHANGE ACCEPTED
CTRL
CTRL CCNA
CCNA 1 CCN ADDRESS SCROLLING STOPS
1VALUE FLASHES
2 SELECT 2 (SEE NOTE 1)
CCNA 2 CCN ADDRESS CHANGE ACCEPTED
CCNA
CCNB
CCNB 0 CCN BUS NUMBER DEFAULT 0 (SEE NOTE 2)
CCNB
OPT2
RSET PROCEED TO SUBMODE RSET
RSET CRST COOLING RESET TYPE
LLEN LEAD/LAG CHILLER ENABLE 15 ITEMS
LLEN DSBL SCROLLING STOPS
DSBL VALUE FLASHES
ENBL SELECT ENBL
LLEN ENBL LEAD/LAG CHILLER ENABLE CHANGE ACCEPTED
LLEN
MSSL MASTER/SLAVE SELECT
MSSL MAST SCROLLING STOPS
MAST VALUE FLASHES
SLVE SELECT SLAVE
MSSL SLVE MASTER/SLAVE SELECT CHANGE ACCEPTED
MSSL
RSET SLAVE COMPLETE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ESCAPE