40
Table 17 — Configuration Mode and Sub-Mode Directory (cont)
LEGEND
SUB-MODE
KEYPAD
ENTRY
ITEM
MARQUEE
DISPLAY RANGE
NAVIGATOR
DISPLAY RANGE
ITEM EXPANSION COMMENT
RSET
(cont)
SHNM 0 - 99 0 - 99
LOADSHED GROUP
NUMBER
Default: 0
SHDL 0 - 60% 0 - 60%
LOADSHED DEMAND
DELTA
Default: 0
SHTM 0 - 120 0 - 120
MAXIMUM LOADSHED
TIME
Default: 60 minutes
DLS1 0 - 100% 0 - 100%
DEMAND LIMIT
SWITCH 1
Default: 80%
DLS2 0 - 100% 0 - 100%
DEMAND LIMIT
SWITCH 2
Default: 50%
LLEN ENBL-DSBL ENBL-DSBL
LEAD/LAG CHILLER
ENABLE
Default: DSBL
MSSL SLVE-MAST SLVE-MAST
MASTER/SLAVE
SELECT
Default: Master
SLVA 0 - 239 0 - 239 SLAVE ADDRESS Default: 0
LLBL ENBL-DSBL ENBL-DSBL
LEAD/LAG BALANCE
SELECT
Default: DSBL
LLBD 40 - 400HRS 40 - 400 HRS
LEAD/LAG BALANCE
DELTA
Default: 168 hours
LLDY 0 - 30 MIN 0 - 30 MIN LAG START DELAY Default: 5 minutes
SLCT
CLSP 0 - 5 SINGLE
DUAL SWITCH
DUAL 7 DAY
DUAL CCN OCC
4-20 INPUT
EXTERNAL POT
COOLING SETPOINT
SELECT
Default: 0
0 = Single
1 = Dual Switch
2 = Dual 7 Day
3 = Dual CCN Occupancy
4 = 4-20 Input
5 = Set Point Potentiometer
HTSP 0 - 4 0 - 4 HEATING SETPOINT SELECT Not Supported (Default: 0)
RL.S ENBL-DSBL ENBL-DSBL RAMP LOAD SELECT Default: DSBL
CRMP
0.2 - 2.0° F
(0.1 - 1.1° C)
0.2 - 2.0° F
(0.1 - 1.1° C)
COOLING RAMP LOADING Default: 1.0
HRMP
0.2 - 2.0° F
(0.1 - 1.1° C)
0.2 - 2.0° F
(0.1 - 1.1° C)
HEATING RAMP LOADING Not Supported (Default: 1.0)
HCSW COOL-HEAT COOL-HEAT HEAT COOL SELECT Not Supported (Default: COOL)
Z.GN 1.0 - 4.0 1.0 - 4.0 DEADBAND MULTIPLIER Default: 1.0
CCN — Carrier Comfort Network
EMM — Energy Management Module
EXV — Electronic Expansion Valve
LCW — Leaving Chilled Water
ENTER