Carrier 23XL Specifiche

Navigare online o scaricare Specifiche per no Carrier 23XL. Carrier 23XL Specifications Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 104
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 0
Start-Up, Operation, and Maintenance
Instructions
SAFETY CONSIDERATIONS
Screw liquid chillers are designed to provide safe and reli-
able service when operated within design specifications. When
operating this equipment, use good judgment and safety pre-
cautions to avoid damage to equipment and property or in-
jury to personnel.
Be sure you understand and follow the procedures and safety
precautions contained in the machine instructions, as well
as those listed in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet from
rupture disc or relief valve must be vented outdoors in accordance with
the latest edition of ANSI/ASHRAE 15 (American National Standards
Institute, American Society of Heating, Refrigeration, and Air Condi-
tioning Engineers), latest edition. The accumulation of refrigerant in an
enclosed space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/ASHRAE 15,
especially for enclosed and low overhead spaces. Inhalation of high
concentrations of vapor is harmful and may cause heart irregularities,
unconsciousness, or death. Misuse can be fatal. Vapor is heavier than
air and reduces the amount of oxygen available for breathing. Product
causes eye and skin irritation. Decomposition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a machine for
any purpose. Oxygen gas reacts violently with oil, grease, and other
common substances.
NEVER EXCEED specified test pressures. VERIFY the allowable test
pressure by checking the instruction literature and the design pressures
on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry
nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and func-
tioning before operating any machine.
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until
all refrigerant (liquid and vapor) has been removed from chiller. Traces
of vapor should be displaced with dry air or nitrogen and the work area
should be well ventilated. Refrigerant in contact with an open flame
produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig machine sections or the
entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified
electrician.
DO NOT WORK ON electrical components, including control centers,
switches, starters, or oil heater (if applicable) until you are sure ALL
POWER IS OFF and no residual voltage can leak from capacitors or
solid-state components.
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK
IS INTERRUPTED, confirm that all circuits are deenergized before
resuming work.
DO NOT syphon refrigerant.
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes.
USE SAFETY GOGGLES. Wash any spills from the skin with soap
and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH
EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cylinder.
Dangerous over pressure can result. When it is necessary to heat re-
frigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to
refill them. It is DANGEROUS AND ILLEGAL. When cylinder is emp-
tied, evacuate remaining gas pressure, loosen the collar, and unscrew
and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to the
machine. The introduction of the wrong refrigerant can cause damage
or malfunction to this machine.
Operation of this equipment with refrigerants other than those cited
herein should comply with ANSI/ASHRAE 15 (latest edition). Contact
Carrier for further information on use of this machine with other
refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while ma-
chine is under pressure or while machine is running. Be sure pressure
is at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other re-
lief devices AT LEAST ONCE A YEAR. If machine operates in a cor-
rosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief de-
vice when corrosion or build-up of foreign material (rust, dirt, scale,
etc.) is found within the valve body or mechanism. Replace the
device.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to act
as projectiles.
DO NOT STEP on refrigerant lines. Broken lines can whip about and
release refrigerant, causing personal injury.
DO NOT climb over a machine. Use platform, catwalk, or staging. Fol-
low safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move
inspection covers or other heavy components. Even if components are
light, use mechanical equipment when there is a risk of slipping or
losing your balance.
BE AWARE that certain automatic start arrangements CAN ENGAGE
THE STARTER, TOWER FAN, OR PUMPS. Open the disconnect ahead
of the starter, tower fan, or pumps. Shut off the machine or pump be-
fore servicing equipment.
USE only repair or replacement parts that meet the code requirements
of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines,
liquid, gases, or semisolids without the permission of your process con-
trol group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has been
completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or other
items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the nut
has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for corro-
sion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure
relief device to prevent a build-up of condensate or rain water.
23XL
50/60 Hz
Hermetic Screw Liquid Chillers
With HCFC-22 and HFC-134a
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Tab 5e
PC 211 Catalog No. 532-302 Printed U.S.A. Form 23XL-2SS Pg 1 12-94 Replaces: 23XL-1SS
Vedere la pagina 0
1 2 3 4 5 6 ... 103 104

Sommario

Pagina 1 - Instructions

Start-Up, Operation, and MaintenanceInstructionsSAFETY CONSIDERATIONSScrew liquid chillers are designed to provide safe and reli-able service when ope

Pagina 2 - CONTENTS

LEGENDHGBP — Hot Gas BypassRefrigerant Liquid FlowRefrigerant Vapor FlowOil and Refrigerant Vapor FlowOil FlowFig. 4 — Refrigerant Oil Flow Schematic

Pagina 3 - CONTENTS (cont)

Fig. 61 — Typical Machine Power Panel, Starter Assembly, and Motor (Frame 4 Machines)100

Pagina 4

Fig. 62 — Typical Wye-Delta Unit Mounted Starter Wiring Schematic101

Pagina 5 - REAR VIEW

Fig. 62 — Typical Wye-Delta Unit Mounted Starter Wiring Schematic (cont)102

Pagina 6

INDEX23XL Machine Familiarization, 4Abbreviations and Explanations, 4Adding Refrigerant, 63Adjusting the Refrigerant Charge, 63After Extended Shutdown

Pagina 7

To Stop the Machine, 58Tower-Fan Relay, 31Troubleshooting Guide, 68Unit Mounted Solide-State Starter, 11Unit Mounted Wye Delta Starter, 12Using The Op

Pagina 8

In addition, the PIC Controls minimize oil loss to the cooleronce the rotor inlet temperature sensor detects hot oil drain-ing down the suction pipe.I

Pagina 9

These starters operate by reducing the starting voltage. Thestarting torque of a motor at full voltage is typically 125%to 175% of the running torque.

Pagina 10

CONTROLSControls DefinitionsANALOG SIGNAL — An analog signal varies in propor-tion to the monitored source. It quantifies values betweenoperating limits

Pagina 11 - STARTING EQUIPMENT

*Some 23XL machines will have both an oil temperature sensor and an oil level safety switch (two separate components).Fig. 11 — 23XL Control and Senso

Pagina 12

*Some 23XL machines will have both an oil temperature sensor and an oil level safety switch (two separate components).Fig. 12 — 23XL Control and Senso

Pagina 13 - Controls Definitions

Fig. 13 — Control Sensors (Temperature)Fig. 14 — Control Sensors(Pressure Transducer, Typical)LEGEND1—LID 4—5-Volt TransducerPower Supply2—PSIO 5—6-Pa

Pagina 14

LOCAL INTERFACE DEVICE (LID) — The LID is mountedin the control center and allows the operator to interface withthe PSIO or other CCN devices. It is t

Pagina 15

MENU STRUCTURE — To perform any of the operationsdescribed below, the PIC must be powered up and have suc-cessfully completed its self test.• Press NE

Pagina 16

Fig. 20 — 23XL Menu Structure19

Pagina 17

CONTENTSPageSAFETY CONSIDERATIONS ...1INTRODUCTION ...4ABBREVIATIONS AND EXPLANATIONS ...423XL MACHINE

Pagina 18

Fig. 21 — 23XL Service Menu Structure20

Pagina 19 - Fig. 20 — 23XL Menu Structure

For Discrete Points — Press START or STOP to se-lect the desired state.For Analog Points — Press INCREASE orDECREASEto select the desired value.3. Pre

Pagina 20

9. Either return to Step 4 to select another period or override or press EXITagain to leave the current timeschedule screen and save the changes.10. H

Pagina 21

The proportional band can be viewed/modified on the LID.There are two response modes, one for temperature re-sponse above the control point, the other

Pagina 22 - PIC System Functions

Table 3 — LID ScreensIMPORTANT: The following notes apply to all Table 3examples:1. Only 12 lines of information will appear on the LID screen at anyg

Pagina 23

EXAMPLE3—STATUS03 DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press STATUS.3. Scroll down to highlight STATUS03.

Pagina 24 - Table 3 — LID Screens

Table 3 — LID Screens (cont)EXAMPLE 6 — LEAD/LAG CONFIGURATION DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press

Pagina 25

EXAMPLE 8 — SERVICE2 DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press SERVICE.3. Scroll down to highlight EQUIP

Pagina 26 - Table 3 — LID Screens (cont)

Table 3 — LID Screens (cont)EXAMPLE 11 — MAINTENANCE (MAINT02) DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press

Pagina 27

Ramp Loading Control — The ramp loading controlslows down the rate at which the compressor loads up. Thiscontrol can prevent the compressor from loadi

Pagina 28

CONTENTS (cont)PageInput the Local Occupied Schedule(OCCPC01S) ...52Selecting Refrigerant Type ...53• TO CO

Pagina 29

Table 4 — Protective Limits and Control SettingsMONITORED PARAMETER LIMIT APPLICABLE COMMENTSTEMPERATURE SENSORSOUT OF RANGE−40 to 245 F (−40 to 118.3

Pagina 30 - Flow Switch (Field Supplied)

Table 5 — Capacity OverridesOVERRIDECAPACITYCONTROLVIEW/MODIFYON LIDTABLEFIRST STAGE SETPOINTSECOND STAGESET POINTOVERRIDETERMINATIONDefaultValueConfig

Pagina 31

Water/Brine Reset — Three types of chilled water orbrine reset are available and can be viewed or modified onthe Equipment Configuration menu Config tabl

Pagina 32 - Fig. 24 and 25) —

Lead/Lag ControlIMPORTANT: Lead/lag control is only available onmachines with PSIO Software Version 13 or higher.Lead/lag is a control system process

Pagina 33 - Lead/Lag Control

Standby Chiller Configuration and Operation — The con-figured standby chiller is identified as such by having theLEAD/LAG SELECT configured to the value o

Pagina 34 - Ice Build Control

ICE BUILD INITIATION — The Ice Build Time Scheduleprovides the means for activating ice build. The ice buildtime table is named OCCPC02S.If the Ice Bu

Pagina 35

CHANGING REFRIGERANT TYPES — To select refrig-erant type, go to the Control Test table. Whenever the re-frigerant type is changed, the ATTACH TO NETWO

Pagina 36

4. Press NEXT until Holidef is highlighted. This isthe Holiday Definition table.5. Press SELECT to enter the Data Table Select screen.This screen lists

Pagina 37 - Local Start-Up —

Shutdown Sequence — Shutdown of the machine canoccur if any of the following events happen:• the STOP button is pressed for at least one second (theal

Pagina 38

When the machine is in RECYCLE mode, the chilled wa-ter pump relay remains energized so that the chilled watertemperature can be monitored for increas

Pagina 39

CONTENTS (cont)Control Test ...69Control Modules ...80• RED LED• GREEN LEDsNotes on Module Opera

Pagina 40

Leak Test Machine — Due to regulations regarding re-frigerant emissions and the difficulties associated with sepa-rating contaminants from refrigerant

Pagina 41

Fig. 30 — 23XL Leak Test Procedures41

Pagina 42

Fig. 31 — Typical Optional Pumpout System Piping Schematic with Storage Tank (Frame 1 and 2 Machines)42

Pagina 43

Fig. 32 — Typical Optional Pumpout System Piping Schematic With Storage Tank (Frame 4 Machines)43

Pagina 44 - (Frame 1 and 2 Machines)

Fig. 33 — Typical Optional Pumpout System Piping Schematic Without Storage Tank(Frame 1 and 2 Machines)44

Pagina 45 - (Frame 4 Machines)

Fig. 34 — Typical Optional Pumpout System Piping Schematic Without Storage Tank(Frame 4 Machines)45

Pagina 46

Table 6A — HCFC-22 Pressure — Temperature (F)TEMPERATURE (F)PRESSURE (psi)Absolute Gage-50 11.67 6.154*-48 12.34 4.829*-46 13.00 3.445*-44 13.71 2.002

Pagina 47

Table 6C — HFC-134a Pressure — Temperature (F)TEMPERATURE, F PRESSURE (psig)0 6.502 7.524 8.606 9.668 10.7910 11.9612 13.1714 14.4216 15.7218 17.0620

Pagina 48

Standing Vacuum Test — When performing the stand-ing vacuum test or machine dehydration, use a manometeror a wet bulb indicator. Dial gages cannot ind

Pagina 49 - Check Starter

Inspect WiringDo not apply any kind of test voltage if the machine isunder a dehydration vacuum. Insulation breakdown andserious damage may result.1.

Pagina 50

FRONT VIEW1—Power Panel2—Local Interface Display (LID) Control Center3—ASME Nameplate, Cooler4—Cooler Refrigerant Isolation Valve5—ASME Nameplate, Eco

Pagina 51 - 60 seconds

MECHANICAL-TYPE STARTERS1. Check all field wiring connections for tightness, clear-ance from moving parts, and correct connection.2. Check the contacto

Pagina 52

CUTLER-HAMMERt SOLID-STATE STARTERSThis equipment is at line voltage when ac power is con-nected. Pressing the STOP button does not remove volt-age. U

Pagina 53

Table 7 — Potentiometer AdjustmentDIALADJUSTMENT RANGEFUNCTIONFACTORYSETTINGMinimum(CCW)Maximum(CW)Starting Current 100% 400% Sets initial startingcur

Pagina 54

Selecting Refrigerant Type — The 23XL control mustbe configured for the refrigerant being used, either HCFC-22or HFC-134a.TO CONFIRM REFRIGERANT TYPE —

Pagina 55 - Compressor —

Minimum Load DT1:46.5 −44 = 2.5 F (8.1 −6.7 = 1.4 C)Minimum Load DP1:121 − 73 = 45 psid (834 - 503 = 331 kPad)To avoid unnecessary opening of the hot

Pagina 56 - Check Rotation

Table 8 — Control Test Table FunctionsTESTS TO BE PERFORMED DEVICES TESTED1. Automated Tests* Operates the second through seventh tests2. PSIO Thermis

Pagina 57

Table 9 — Refrigerant ChargesCOOLER SIZE ECONOMIZERREFRIGERANTHCFC-22 HFC-134alb kg lb kg10,11NO 600 272 * *YES 650 295 * *20,21NO 700 318 * *YES 750

Pagina 58

If rotation is proper , allow the compressor to come up tospeed.NOTE: Starters may have phase protection and will not al-low a start if the phase is n

Pagina 59

OPERATING INSTRUCTIONSOperator Duties1. Become familiar with refrigeration machine and relatedequipment before operating the machine.2. Prepare the sy

Pagina 60

Carefully make all regular preliminary and running sys-tem checks. Perform a Control Test before start-up. If the oillevel appears abnormally high, th

Pagina 61 - TRANSFER PROCEDURES

FRONT VIEW1—Compressor Nameplate (Hidden)2—Power Panel3—Local Interface Display (LID) Control Center4—ASME Nameplate, Cooler5—Cooler6—Vessel Separatio

Pagina 62

Plant MACHINE MODEL NO. MACHINE SERIAL NO. REFRIGERANT TYPEDATE COOLER CONDENSER COMPRESSOROPER-ATORINITIALSREMARKSTIMERefrigerant Water Refrigerant W

Pagina 63

PUMPOUT AND REFRIGERANTTRANSFER PROCEDURESPreparation —The 23XL may come equipped with iso-lation valves and/or a pumpout system/optional storage tank

Pagina 64

d. Gradually crack open valve 5 to increase machine pres-sure to 68 psig (469 kPa) [35 psig (141 kPa)]. Slowlyfeed refrigerant to prevent freeze up.e.

Pagina 65

g. Turn off pumpout condenser water.VALVE 1a1b2345811121314151617CONDITION C C CCCCC C CCCCCCh. Proceed to Pumpdown test on the LID to turn off ma-chi

Pagina 66

Refrigerant Leak Rate — ASHRAE recommends thatmachines should be immediately taken off line and repairedif the refrigerant leakage rate for the entire

Pagina 67

Change the oil after the first year of operation. Then, changethe oil at least every three years, or as needed. However, ifa continuous oil monitoring

Pagina 68

Oil Specification — If oil is to be added, it must meetthe following Carrier specifications:• Carrier Part Number ...PP23BZ104• Oil type

Pagina 69

Hard scale may require chemical treatment for its pre-vention or removal. Consult a water treatment specialistfor proper treatment.Water Leaks — Water

Pagina 70 - LEGEND FOR TABLE 10, A - N

Ordering Replacement Chiller Parts — When or-dering Carrier specified parts, the following information mustaccompany an order.• machine model number an

Pagina 71 - E. NORMAL OR AUTO.-RESTART

If the transducer value does not move to 0 psig (0 kPa),the transducer will return to the original reading. If thepressure is within the allowed range

Pagina 72 - F. START-UP FAILURES

Cooler — This vessel (also known as the evaporator) islocated underneath the compressor. The cooler is main-tained at low temperature/pressure so that

Pagina 73

LEGEND FOR TABLE 10, A - N1CR AUX — 1CR Compressor Start ContactCA P— Compressor CurrentCDFL — Condenser Water FlowCHIL S S— Chiller Start/StopCHWS —

Pagina 74

Table 10 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)D. PRE-START FAILURESPRIMARY MESSAGE SE

Pagina 75

Table 10 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)F. START-UP FAILURESPRIMARY MESSAGE SEC

Pagina 76 - L. MACHINE ALERTS

Table 10 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)G. COMPRESSOR JUMPSTART AND REFRIGERANT

Pagina 77

Table 10 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)I. NORMAL RUN OVERRIDES ACTIVE (ALERTS)

Pagina 78

K. MACHINE PROTECT LIMIT FAULTSExcessive numbers of the same fault can lead to severemachine damage. Seek service expertise.PRIMARY MESSAGE SECONDARY

Pagina 79

Table 10 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)L. MACHINE ALERTSPRIMARY MESSAGE SECOND

Pagina 80 - Notes on Module Operation

Table 10 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)N. ADDITIONAL TROUBLESHOOTING INFORMATI

Pagina 81

Table 11 — Thermistor Temperature (F) vs Resistance/Voltage DropTEMPERATURE VOLTAGE RESISTANCE(F) DROP (V) (OHMS)−25.0 4.821 98010−24.0 4.818 94707−23

Pagina 82

Table 12 — Thermistor Temperature (C) vs Resistance/Voltage DropTEMPERATURE VOLTAGE RESISTANCE(C) DROP (V) (Ohms)−40 4.896 168 230−39 4.889 157 440−38

Pagina 83

• positions the slide valve for capacity control. The slide valveis connected to a piston via a rod. The position of the pis-ton, which rides in a cyl

Pagina 84 - FLT — Fault LED

Control ModulesTurn controller power off before servicing controls. Thisensures safety and prevents damage to controller.The Processor module (PSIO),

Pagina 85

Processor Module (PSIO) (Fig. 46)INPUTS — Each input channel has 3 terminals; only 2 ofthe terminals are used. Application of machine determineswhich

Pagina 86

Terminal block connections are provided on the optionsmodules. All sensor inputs are field wired and installed. Op-tions module number 1 can be factory

Pagina 87

Solid-State Starters — Troubleshooting guides per-taining to the operation of the solid-state starters may be foundin Fig. 49-55 and Tables 13 and 14.

Pagina 88

ELECTRONIC PROTECTION RELAY (EPR) — On Cutler-Hammer solid state starters, the EPR is designed to providean alternative to conventional motor protecti

Pagina 89

Table 13 — Benshaw, Inc. Solid-State Starter Troubleshooting GuidePROBLEM PROBABLE CAUSES AREA OF CORRECTIONBIPCRS6AK board phase correctnot on.1. L1

Pagina 90

Table 14 — Cutler-HammerT Solid-State Starter Troubleshooting GuidePROBLEM PROBABLE CAUSE AREA OF CORRECTION(CB) trips (electrically operateddisconnec

Pagina 91

SCR — Silicon Control RectifierFig. 54 — Typical Solid-State Starter, General Operation Troubleshooting Guide87

Pagina 92

Fig. 55 — Typical Solid-State Starter, Starter Fault (Motor Will Not Start) Troubleshooting Guide88

Pagina 93

Physical Data — For operator convenience during trouble-shooting, additional details regarding compressor torque speci-fications, physical data, electr

Pagina 94

LEGENDHGBP — Hot Gas BypassRefrigerant Liquid FlowRefrigerant Vapor FlowOil and Refrigerant Liquid FlowOil and Refrigerant Vapor FlowOil FlowFig. 3 —

Pagina 95

Table 18 — Optional Storage Tank and/or Pumpout System Physical DataUNITSIZETANK OUTSIDEDIAMETERDRY WEIGHTMAXIMUM REFRIGERANT CAPACITYASHRAE/ANSI 15 A

Pagina 96

Table 20A — 23XL Waterbox Cover Weights (Frame 1 and 2 Machines)*HEAT EXCHANGERWATERBOXDESCRIPTIONPSI(kPa)FRAME 1 FRAME 2lbs kg lbs kgCooler orCondens

Pagina 97

Table 21 — 23XL Compressor Torque Specification Chart for Metric and American FastenersITEMCAP SCREWSIZE AND TYPEGRADE ASSEMBLY LOCATIONTORQUENm Lb-Ft

Pagina 98

IMPORTANT: Refer to certified drawings for addi-tional information. Certified drawings are available uponrequest.LEGENDRequired Power WiringRequired Con

Pagina 99

IMPORTANT: Refer to certified drawings for addi-tional information. Certified drawings are available uponrequest.LEGENDRequired Power WiringRequired Con

Pagina 100

Fig. 58 — Typical Electronic PIC Controls Wiring Schematic (Frame 1 and 2 Machines)95

Pagina 101

Fig. 58 — Typical Electronic PIC Controls Wiring Schematic (Frame 1 and 2 Machines) (cont)96

Pagina 102

Fig. 59 — Typical Electronic PIC Controls Wiring Schematic (Frame 4 Machines)97

Pagina 103

Fig. 59 — Typical Electronic PIC Controls Wiring Schematic (Frame 4 Machines) (cont)98

Pagina 104

Fig. 60 — Typical Machine Power Panel, Starter Assembly, and Motor (Frame 1 and 2 Machines)99

Commenti su questo manuale

Nessun commento