
If rotation is proper , allow the compressor to come up to
speed.
NOTE: Starters may have phase protection and will not al-
low a start if the phase is not correct. Instead, a ‘‘STARTER
FAULT’’ message will occur if this happens.
NOTES ON SOLID-STATE STARTERS
1. When the compressor is energized to start by the 1CR
relay, confirm that the ‘‘Relay On LED’’is lit on the starter
SCR control board. The compressor motor should start to
turn immediately when this light comes on. If not, adjust
the start torque potentiometer in a clockwise direction.
2. Observe that all 6-gate LEDs are lit on the starter SCR
control board.
3. The factory setting should bring the motor to full
voltage in 3 to 5 seconds on Wye delta starters or 8 to 10
seconds on solid-state starters. If the setting is not cor-
rect, adjust the ramp potentiometer counterclockwise for
a shorter time, clockwise for a longer time.
Check Oil Pressure and Compressor Stop
1. Two minutes after start-up, note the oil pressure reading
on the LID default screen. The value is equal to the dif-
ference between the oil and evaporator pressure trans-
ducer readings. The minimum oil pressure is 20-40 psi
(138-276 kPa) [7-40 psi (48-276 kPa)]. The oil and evapo-
rator pressure transducer readings can be observed on the
Status01 table. A normal full load reading is approxi-
mately 120 psi (827 kPa) [78 psi (538 kPa)].
2. Press the STOP softkey and listen for any unusual sounds
from the compressor as it coasts to a stop.
Calibrate Motor Current Demand Setting
NOTE: Entering condenser water temperature must equal de-
sign for compressor to meet 100% RLA at designs tons.
1. Make sure that the compressor motor rated load amps in
the Service1 table has been configured. Place an ammeter
on the line that passes through the motor load current trans-
former on the motor side of the power factor correction
capacitors (if provided).
2. Set the chilled water set point to the desired value.
Highlight the appropriate chilled water set point on
the set point screen then press SELECT
. Press
INCREASE
or DECREASE to bring the value top
desired value. Press ENTER
when equal.
3. Start the compressor and establish a steady motor current
by overriding the Active Demand Limit on the
Status01 table. Highlight this point, then press
SELECT
. Press INCREASE or DECREASE to
bring the value between 70% and 100% RLA. Press
ENTER
when finished.
4. Compare the compressor motor amps value on the
Status01 table to the actual amps shown on the ammeter
on the starter. Adjust the amps value on the LID to the
actual value seen at the starter if there is a difference. High-
light the amps value then press SELECT
. Press
INCREASE
or DECREASE to bring the value to that
indicated on the ammeter. Press ENTER
when equal.
The adjustments should not be performed in intervals of
more than 10 amps.
5. Gradually increase the Active Demand Limit and repeat
Step 4.
6. When calibration is complete, make sure that the Active
Demand Limit is released to PIC control.
To Prevent Accidental Start-Up — The PIC can be
set up so that start-up of the unit is more difficult than just
pressing the LOCAL
or CCN softkeys during machine
service or when necessary. By accessing the Status01
table, and highlighting the chiller Start/Stop line, the value
can be overridden to stop by pressing SELECT
and then
the STOP
and ENTER softkeys. ‘‘SUPVSR’’ will ap-
pear after the value. When attempting to restart, remember
to release the override. The default machine message line
will also state that the Start/Stop has been set to ‘‘Start’’ or
‘‘Stop’’ when the value is overridden.
Check Machine Operating Conditions — Check
to be sure that machine temperatures, pressures, water flows,
and oil and refrigerant levels indicate that the system is func-
tioning properly.
Instruct the Operator — Check to be sure that the op-
erator(s) understands all operating and maintenance proce-
dures. Point out the various machine parts and explain their
function as part of the complete system.
COOLER-CONDENSER — Float valve, relief devices, re-
frigerant charging valve, temperature sensor locations, pres-
sure transducer locations, Schrader fittings, waterboxes and
tubes, and vents and drains.
OPTIONAL STORAGE TANK AND PUMPOUT SYS-
TEM — Transfer valves and pumpout system, refrigerant
charging and pumpdown procedure, and relief devices.
MOTOR COMPRESSOR ASSEMBLY — Slide valve
assembly, motor cooling system, temperature and pressure
sensors, motor temperature sensors, and compressor
serviceability.
MOTOR COMPRESSOR LUBRICATION SYSTEM — Oil
heater (Frame 1 and 2 machines), oil charge and specifica-
tion, synthetic oil, operating and shutdown oil level, tem-
perature and pressure, and oil charging connections.
COMPRESSOR LUBRICATION SYSTEM — Oil sight glass,
operating and shutdown oil level, temperature and pressure
transducers, isolatable oil filter assembly, oil charging and
drain connections, rotor inlet sensors, discharge pressure trans-
ducer, and oil charge and specifications.
OIL SEPARATION SYSTEM — Oil sight glasses, sensors,
muffler, and oil level switch (Frame 4 machines only).
CONTROL SYSTEM — CCN and Local start, reset, menu,
softkey functions, LID operation, occupancy schedule, set
points, safety controls, and auxiliary and optional controls.
AUXILIARY EQUIPMENT — Starters and disconnects, sepa-
rate electrical sources, pumps, and cooling tower.
DESCRIBE MACHINE CYCLES — Refrigerant, motor cool-
ing, lubrication, and oil reclaim.
REVIEW MAINTENANCE — Scheduled, routine, and ex-
tended shutdowns, importance of a log sheet, importance of
water treatment and tube cleaning, and importance of main-
taining a leak-free machine.
SAFETY DEVICES AND PROCEDURES — Electrical dis-
connects, relief device inspection, and handling refrigerant.
CHECK OPERATOR KNOWLEDGE — Start, stop, and shut-
down procedures, safety and operating controls, refrigerant
and oil charging, and job safety.
REVIEW THE START-UP, OPERATION, AND MAINTE-
NANCE MANUAL.
57
Commenti su questo manuale