Minimum Load DT1:
46.5 −44 = 2.5 F (8.1 −6.7 = 1.4 C)
Minimum Load DP1:
121 − 73 = 45 psid (834 - 503 = 331 kPad)
To avoid unnecessary opening of the hot gas bypass valve,
add 5 psi (35 kPa) at DP1 from these conditions:
DT1 = 2.5 F (1.4 C)
DP1 = 50 psid (345 kPad) [30 psid (207 kPad)]
If opening of the hot gas bypass valve occurs too soon or too
late for the present conditions these parameters should be
changed by the operator. Only the minimum load points change
is required.
Energizing the hot gas bypass solenoid valve with the ball
valve fully open and the cold condenser water at a very low
temperature will result in the equalization of evaporator and
condenser pressure. This will result in a ‘‘Low Oil Pressure’’
alarm. See the Lubrication Cycle section on page 7.
MODIFY EQUIPMENT CONFIGURATION AS NECES-
SARY — The Equipment Configuration table has tables to
select and view or modify. Carrier’s certified drawings will
have the configuration values required for the jobsite. Modify
these tables only if requested.
Config Table Modifications — Change the values in this table
per job data. See certified drawings for values. Modifica-
tions include:
• chilled water reset
• entering chilled water control (Enable/Disable)
• 4-20 mA demand limit
• auto restart option (Enable/Disable)
• remote contact option (Enable/Disable)
Owner-Modified CCN Tables — The following tables are de-
scribed for reference only.
Occdefcs Table Modifications — The Occdefcs tables con-
tain the Local and CCN time schedules, which can be modi-
fied here, or in the Schedule menu selection as described
previously.
Holidef Table Modifications — The Holidef tables configure
the days of the year that holidays are in effect. See the holi-
day paragraphs in the Controls section for more
details.
Brodefs Table Modifications — The Brodefs screen defines
the outside air temperature sensor and humidity sensor (if
installed). It will define the start and end of daylight savings
time. Enter the dates for the start and end of daylight savings
if required for the location. Brodefs also will activate the
Broadcast function which enables the holiday periods that
are defined on the LID.
Other Tables — The Alarmdef, Cons-def, and Runt-def con-
tain tables for use with a CCN system. See the applicable
CCN manual for more information on these tables.
These tables can only be defined through a CCN Building
Supervisor.
CHECK VOLTAGE SUPPLY — Access the Status01 table
and read the actual line voltage. This reading should be equal
to the incoming power to the starter. Use a voltmeter to check
incoming power at the starter power leads. If the readings
are not equal, an adjustment can be made to the 24-v input
to the SMM at a potentiometer located in the low voltage
section to equalize the two readings.
PERFORM AN AUTOMATED CONTROL TEST — Check
the safety controls status by performing an automated con-
trol test. Access the Control Test table and select the
Automated Tests function (Table 8).
The automated control test will check all outputs and in-
puts for function. It will also set the refrigerant type. The
compressor must be in the OFF mode in order to operate the
controls test and the 24-v input to the SMM must be in range
(per line voltage percent on Status01 table). The OFF mode
is caused by pressing the STOP pushbutton on the LID lo-
cated on the left side of the four softkeys). Each test will ask
the operator to confirm that the operation is occurring, and
whether or not to continue. If an error occurs, the operator
has the choice to try to address the problem as the test is
being run or to note the problem and proceed to the next
test.
When the test is finished, or the EXIT
softkey is pressed,
the test will be stopped and the Control Test table will be
displayed. If a specific automated test procedure is not com-
pleted, access that particular controls test to test the function
when ready. The Control Test table is described as
follows:
Automated Tests As described above, a complete
controls test.
PSIO Thermistors Check of all PSIO
thermistors only.
Option Module
Thermistors
Check of all option
module thermistors.
Transducers Check of all transducers.
Slide Valve Check of the slide valve
operation.
Pumps Check operation of pump outputs,
either all pumps can be
activated, or individual pumps
can be activated.
The test will also test
the associated input such as
flow or pressure.
Discrete Outputs Activation of all on/off
outputs or individual on/off outputs.
Pumpdown Pumpdown prevents the low
refrigerant alarm during
evacuation so refrigerant
can be removed from the unit.
Pumpdown also locks the
compressor off and
starts the water pumps.
Terminate Lockout Charges refrigerant and enables
the chiller to run after pumpdown
lockout.
Refrigerant Type* Sets type of refrigerant used:
HCFC-22 or HFC-134a.
*Make sure to Attach to Local Device after changing refrigerant type.
Refer to Selecting Refrigerant Type section on page 53.