
Selecting Refrigerant Type — The 23XL control must
be configured for the refrigerant being used, either HCFC-22
or HFC-134a.
TO CONFIRM REFRIGERANT TYPE — Confirm that the
correct refrigerant type is indicated by entering the Service
menu and selecting Control Test. See Fig. 21. Select Refrig-
erant Type. The screen will display the current refrigerant
setting. Press EXIT softkey to leave the screen without changes.
TO CHANGE REFRIGERANT TYPE — Enter the Service
menu and select Control Test. See Fig. 21. Select Refriger-
ant Type. The screen will display the current refrigerant set-
ting. Press the YES softkey to change the current setting.
Next, move to the Attach To Network Device menu and se-
lect ATTACH TO LOCAL DEVICE to upload the new re-
frigerant tables.
Input Service Configurations — The following con-
figurations require the LID screen to be in the Service por-
tion of the menu.
• password
• input time and date
• LID configuration
• controller identification
• service parameters
• equipment configuration
• automated controls test
PASSWORD — When accessing the Service screens, a pass-
word must be entered. All LIDs are initially set for a pass-
word of 1-1-1-1. This password may be changed in the LID
configuration screen, if desired. See Fig. 21.
INPUT TIME AND DATE — Access the Time and Date
menu on the Service menu. Input the present time of day,
date, and day of the week. ‘‘Holiday Today’’ should only be
configured to ‘‘Yes’’ if the present day is considered a one-
time holiday. This causes the chiller to start and stop as de-
picted by the holiday configuration under the appropriate time
schedule screen.
CHANGE LID CONFIGURATION IF NECESSARY— The
LID Configuration on the service menu is used to view or
modify the LID CCN address, change to English or SI units
and to change the password. If there is more than one ma-
chine at the jobsite, change the LID address on each ma-
chine so that each machine has its own address. Note and
record the new address. Change to SI units, as required, and
change the password, if desired.
MODIFY CONTROLLER IDENTIFICATION, IF NECES-
SARY — The controller identification screen is used to change
the PSIO module address. Change this address for each ma-
chine if there is more than one machine at the job-
site. Write the new address on the PSIO module for future
reference.
Change the LID address if there is more than one machine
on the jobsite. Access the LID configuration screen to view
or modify this address.
INPUT EQUIPMENT SERVICE PARAMETERS AS NEC-
ESSARY — The Equipment Service table has three service
tables: Service1, Service2, and Service3.
Configure Service1 Table —Access Service1 table to modify/
view the following to jobsite parameters:
Chilled Medium Water or Brine
Brine Refrigerant Trip Point Usually 3° F (1.7° C) below design
refrigerant temperature
Hot Gas Bypass Option Is HGBP installed?
Minimum Load Points (T1/P1) Per job data — See Modify Load
Points section
Maximum Load Points (T2/P2) Per job data — See Modify Load
Points section
Motor Rated Load Amps Per job data
Motor Rated Line Voltage Per job data
Motor Rated Line KW Per job data
Line Frequency 50 or 60 Hz (if optional kW
transducer installed)
Compressor Starter Type Reduced voltage or full voltage
NOTE: Other values are left at the default values. These may be changed by
the operator as required. Service2 and Service3 tables can be modified by the
owner/operator, as required.
Modify Minimum and Maximum Load Points (DT1/P1;
D T2/P2) —The pairs of machine load points, located on the
Service1 table, determine when to open the hot gas bypass
solenoid valve. The points should be set based on individual
machine operating conditions.
Close the ball valve, located next to the hot gas solenoid
valve, halfway. The purpose of the ball valve is to act as an
isolation valve and to control the amount of gas flow by ad-
justing the flow to accommodate different frame sizes and
jobsite conditions.
If, after setting the ball valve for these points, any addi-
tional adjustment should be changed by the operator.
Example of configuration: Machine operating parameters
Estimated Minimum Load Conditions:
44 F (6.7 C) LCW
46.5 F (8.1 C) ECW
43 F (6.1 C) Suction Temperature
70 F (21.1 C) Condensing Temperature
Estimated Maximum Load Conditions:
44 F (6.7 C) LCW
54 F (12.2 C) ECW
42 F (5.6 C) Suction Temperature
98 F (36.7 C) Condensing Temperature
Calculate Maximum Load — To calculate maximum load
points, use design load condition data.
Maximum Load DT2:
54 - 44 = 10 F (12.2 - 6.7 = 5.5 C)
Maximum Load DP2:
(Factory Recommended Setting)
200 psi (1379 kPa)[125 psi (862 kPa)]
Calculate Minimum Load — To calculate minimum load con-
ditions, estimate the temperature difference that the cooler
will have at 25% load or lower, then estimate what the suc-
tion and condensing temperatures will be at this point.
Suction Temperature:
43 F (6.1 C) = 73 psig (503 kPa) saturated
refrigerant pressure
Condensing Temperature:
70 F (21.1 C) = 121 psig (834 kPa) saturated
refrigerant pressure
53
Commenti su questo manuale