Carrier 23XL Specifiche Pagina 7

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 104
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 6
Cooler This vessel (also known as the evaporator) is
located underneath the compressor. The cooler is main-
tained at low temperature/pressure so that evaporating re-
frigerant can remove heat from water/brine flowing through
its internal tubes.
Condenser The condenser operates at a higher
temperature/pressure than the cooler and has water flow-
ing through its internal tubes to remove heat from the
refrigerant.
Motor-Compressor The motor-compressor main-
tains system temperature/pressure differences and moves the
heat carrying refrigerant from the cooler to the condenser.
Muffler-Oil Separator The muffler provides acous-
tical attenuation.
Refrigerant/oil separation is accomplished by the oil sepa-
rator. Discharge gas enters near the midsection and leaves
near the top, while the separated oil drains out through the
bottom and flows through a horizontal oil sump/filter
assembly (Frame 1 and 2 machines).
Frame 1 and 2 machines have an oil separator and a muf-
fler assembly. On Frame 4 machines, the muffler is located
inside the oil separator.
Control Center The control center is the user inter-
face for controlling the machine and regulating the ma-
chine’s capacity to maintain the proper chilled water
temperature. The control center:
registers cooler, condenser, and lubricating system
pressures
shows machine operating condition and alarm shutdown
conditions
records the total machine operating hours, starts, and the
number of hours the machine has been currently running
sequences machine start, stop, and recycle under micro-
processor control
provides access to other Carrier Comfort Network devices
Factory-Mounted Starter (Optional Accessory)
The starter allows for the proper starting and discon-
necting of electrical energy for the compressor-motor, oil heater
(Frame 1 and 2 machines), and control center.
Storage Vessel (Optional) Two sizes of storage
vessels are available. The vessels have double relief valves,
a magnetically coupled dial-type refrigerant level gage,
a 1-in. FPT drain valve, and a
1
2
-in. male flare vapor
connection for the pumpout unit. A 30-in.-0-400 psi
(-101-0-2750 kPa) gage is also supplied with each unit.
NOTE: If a storage vessel is not used at the jobsite, factory-
installed optional isolation valves may be used to isolate the
machine charge in either the cooler or condenser. An op-
tional pumpout compressor system is used to transfer refrig-
erant from vessel to vessel.
REFRIGERATION CYCLE
The compressor continuously draws refrigerant vapor from
the cooler. As the compressor suction reduces the pressure
in the cooler, the remaining refrigerant boils at a fairly low
temperature (typically 38 to 42 F [3 to 6 C]). The energy
required for boiling is obtained from the water flowing through
the cooler tubes. With heat energy removed, the water be-
comes cold enough for use in an air-conditioning circuit or
process liquid cooling.
After taking heat from the water, the refrigerant vapor is
compressed. Compression adds still more energy, and the re-
frigerant is quite warm (typically 130 to 160 F [54 to
71 C]) when it is discharged from compressor into
condenser.
Relatively cool (typically 65 to 85 F [18 to 29 C]) water
flowing into the condenser tubes removes heat from the re-
frigerant and the vapor condenses to liquid.
The liquid refrigerant passes through orifices into the FLASC
(Flash Subcooler) chamber (Fig. 3 and 4). Since the FLASC
chamber is at a lower pressure, part of the liquid refrigerant
flashes to vapor, thereby cooling the remaining liquid. The
FLASC vapor is recondensed on the tubes which are cooled
by entering condenser water. The liquid then passes through
a float valve assembly which forms a liquid seal to keep FLASC
chamber vapor from entering the cooler.
An optional economizer can be installed between the con-
denser and cooler. In this case, the float valve meters the
refrigerant liquid into the economizer. Pressure in this cham-
ber is intermediate between condenser and cooler pressures.
At this lower pressure, some of the liquid refrigerant flashes
to gas, cooling the remaining liquid. The flash gas, having
absorbed heat, is returned directly to the compressor at a point
after suction cutoff (Fig. 5). Here it is mixed with gas from
the suction cut-off point to produce an increase in the mass
flow of refrigerant transported and compressed without ei-
ther an increase in suction volume or a change in suction
temperature. Rather than providing the same capacity with
less power, the compressor provides substantially increased
capacity with only a slight increase in power requirements.
The cooled liquid refrigerant in the economizer is me-
tered through an orifice or linear float valve (depending upon
machine design) into the cooler. Because pressure in the cooler
is lower than economizer pressure, some of the liquid flashes
and cools the remainder to evaporator (cooler) temperature.
The cycle is now complete.
MOTOR COOLING CYCLE
The motor is cooled by liquid refrigerant taken from the
bottom of the condenser vessel. The flow of refrigerant is
maintained by the pressure differential that exists due to com-
pressor operation. The refrigerant flows through an isolation
valve, in-line filter/drier, and a sight glass/moisture indicator
(dry-eye), into the motor through the motor spray nozzle.
See Fig. 3 and 4.
The motor spray nozzle is orificed to control refrigerant
flow through the gaps in the rotor and axial vent holes. The
refrigerant collects in the bottom of the motor casing and
then drains into the cooler through the motor cooling drain
line.
The motor is protected by a temperature sensor imbedded
in the stator windings. Motor temperatures above the MO-
TOR WINDING TEMPERATURE OVERRIDE THRESH-
OLD (see Capacity Overrides section, page 29) will over-
ride the chilled water temperature capacity control to hold.
If the motor temperature rises 10 F (5.5 C) above this thresh-
old, the slide valve will unload. If the motor temperature rises
above the safety limit, the compressor will shut down.
LUBRICATION CYCLE
Summary
The 23XL does not require an oil pump.
Oil flow is driven by differential pressure between con-
denser and evaporator. This system pressure difference holds
the potential to push the oil through the oil separator and
filter into the compressor rotors, bearings, and slide valve.
The cycle is referred to as a ‘high side’ oil system. See Fig.
3,4, and 5.
Details The oil system:
lubricates the roller bearings which support the male and
female rotors, and the ball bearings of the 23XL
compressor.
7
Vedere la pagina 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 103 104

Commenti su questo manuale

Nessun commento