
9. Either return to Step 4 to select another period or over
ride or press EXIT
again to leave the current time
schedule screen and save the changes.
10. Holiday Designation may be found in the Service Op-
eration section, page 36. You must assign the month, day,
and duration for the holiday. The Broadcast function in
the Brodefs table also must be enabled for holiday pe-
riods to function.
TO VIEW AND CHANGE SET POINTS (Fig. 23)
1. To view the Set Point table, at the Menu screen press
SETPOINT
.
2. There are 4 set points on this table: Base Demand Limit;
LCW Set Point (leaving chilled water set point); ECW
Set Point (entering chilled water set point); and ICE BUILD
Set Point (PSIO Software Version 13 or higher). Only one
of the chilled water set points can be active at any time.
The type of set point and the ICE BUILD CONFIGU-
RATION are activated in the Service menu.
3. Press NEXT
or PREVIOUS to highlight the desired
set point entry.
4. Press SELECT to modify the highlighted set point.
5. Press INCREASE or DECREASE to change the se-
lected set point value.
6. Press ENTER to save the changes and return to the
previous screen.
SERVICE OPERATION — To view the menu-driven pro-
grams available for Service Operation, see Service Opera-
tion section, page 36. For examples of LID display screens,
see Table 3.
PIC System Functions
NOTE: Throughout this manual, words printed in capital let-
ters and italics are values that may be viewed on the LID.
Operating values for HFC-134a refrigerant, when appli-
cable, follow the HCFC-22 value and are enclosed in brack-
ets. See Table 3 for examples of LID screens. Point names
are listed in the Description column. An overview of LID
operation and menus is given in Fig. 17-23.
CAPACITY CONTROL — The PIC controls the machine
capacity by modulating the slide valve in response to chilled
water temperature changes away from the CONTROL POINT.
The CONTROL POINT may be changed by a CCN network
device, or is determined by the PIC adding any active chilled
water reset to the chilled water SETPOINT. The PIC uses the
PROPORTIONAL INC (Increase) BAND, PROPORTIONAL
DEC (Decrease) BAND, and the PROPORTIONAL ECW (En-
tering Chilled Water) GAIN to determine how fast or slow
to respond. CONTROL POINT may be viewed/overridden
on the Status table Status01 selection.
ENTERING CHILLED WATER CONTROL — If this op-
tion is enabled, the PIC uses ENTERING CHILLED WATER
temperature to modulate the slide valve instead of LEAV-
ING CHILLED WATER temperature. ENTERING CHILLED
WATER control option may be viewed/modified on the Equip-
ment Configuration table Config selection.
DEADBAND — This is the tolerance on the chilled water/
brine temperature CONTROL POINT. If the water tempera-
ture goes outside of the DEADBAND, the PIC opens or closes
the slide valve in response until it is within tolerance. The
PIC may be configured with a 0.5 to 2° F (0.3 to 1.1° C)
DEADBAND. DEADBAND may be viewed or modified on
the Equipment Service table, Service1 table.
For example,a1F(0.6 C) deadband setting controls the
water temperature within ±0.5° F (0.3° C) of the control point.
This may cause frequent slide valve movement if the chilled
water load fluctuates frequently. A setting of 1 F (0.6 C) is
the default setting.
PROPORTIONAL BANDS AND GAIN — Proportional band
is the rate at which the slide valve position is corrected in
proportion to how far the CHILLED WATER/BRINE tem-
perature is from the control point. Proportional gain deter-
mines how quickly the slide valve reacts to how quickly the
temperature is moving from CONTROL POINT.
Fig. 23 — Example of Set Point Screen
22
Commenti su questo manuale